Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Digital outputs | 8 |
| Output type | Digital output, isolated |
| Rated load voltage | 48 V |
| Permissible DC load voltage | 40 V to 140 V |
| Rated output current for signal "1" | 1.5 A |
| Connection | 1x 20-pole |
| Short-circuit protection | Yes; Electronic |
| Channel potential separation | Yes; in groups of 4 |
| Backplane bus separation | Yes; Optocoupler |
| Typical power loss | 7.2 W |
| Conformal coating | Yes |
| Temperature range | -25…+70 °C |
Applications
- Digital input control: The digital outputs can control a digital input.
- Redundant load control: Redundant control of a load is supported using outputs of the same group.
Key Features
- 8 isolated digital outputs: The module has 8 digital outputs with potential separation between channels and between the channels and the backplane bus; the latter uses an optocoupler.
- 48 V DC to 125 V DC load voltage: Rated load voltage is 48 V; the permissible DC range is 40 V to 140 V. Reverse polarity protection is provided through a fuse.
- 1.5 A output current: Rated output current for signal "1" is 1.5 A. For 0 to 40 °C and 40 to 60 °C, the permissible range is 10 mA to 1.5 A.
- Output protection and switching: The digital outputs have electronic short-circuit protection. Switching frequency is up to 25 Hz with resistive load, 0.5 Hz with inductive load, and 10 Hz on lamp load.
- Conformal coating and temperature range: The SIPLUS module has conformal coating and a -25…+70 °C temperature range.
- 1x 20-pole connection: The selected component has a 1x 20-pole connection. Typical power loss is 7.2 W.
Frequently Asked Questions
1. What output channels does Siemens 6AG1322-1CF00-7AA0 provide?
It provides 8 isolated digital outputs.
2. What load voltage and output current does this module support?
Rated load voltage is 48 V, with a permissible DC range of 40 V to 140 V. Rated output current for signal "1" is 1.5 A.
3. What protection and diagnostics are available?
The outputs have electronic short-circuit protection. Alarms, the diagnostics function, diagnostic alarm, wire-break diagnosis, short-circuit diagnosis, fuse-blown diagnosis, and missing-load-voltage diagnosis are not available. A group error SF LED and digital-output status indicators are available.
4. How are the outputs isolated and connected?
The outputs are isolated between channels in groups of 4 and from the backplane bus through an optocoupler. The connection is 1x 20-pole.