Product Overview

Technical Summary

Parameter Value
Module type SIPLUS S7-300 SM 322 digital output module
Digital outputs 8
Rated load voltage 24 V DC
Output current, rated value 2 A
Output current, permissible range, 0 to 40 °C 5 mA to 2.4 A
Output current, permissible range, 40 to 60 °C 5 mA to 2.4 A
Connection 1x 20-pole
Output isolation Between channels in groups of 4; between channels and backplane bus by optocoupler
Output delay with resistive load 100 μs from "0" to "1"; 500 μs from "1" to "0"
Conformal coating Yes
Based on 6ES7322-1BF01-0AA0

Applications

  1. Digital output control: Controls a digital input through the digital outputs.
  2. Redundant load control: Supports redundant control of a load.

Key Features

  1. Digital outputs: 8 digital outputs with 2 A rated output current and 24 V DC rated load voltage.
  2. Electrical protection: The outputs have electronic short-circuit protection and can control a digital input.
  3. Output isolation: The digital outputs are electrically isolated between channels in groups of 4 and from the backplane bus by optocouplers.
  4. Output timing: Maximum output delay is 100 μs from "0" to "1" and 500 μs from "1" to "0" with a resistive load.
  5. Connection and coating: Connection: 1x 20-pole. The module has conformal coating.
  6. Product lifecycle: Product cancellation.

Frequently Asked Questions

1. How many digital outputs does 6AG1322-1BF01-2XB0 have?

It has 8 digital outputs.

2. What load voltage and output current does the module support?

The rated load voltage is 24 V DC and the rated output current is 2 A. For 0 to 40 °C and 40 to 60 °C, the permissible output-current range is 5 mA to 2.4 A.

3. What connection is included?

The module has a 1x 20-pole connection.

4. Does it provide output diagnostics?

It is without diagnostics function, diagnostic alarms, wire-break diagnosis, short-circuit diagnosis, fuse-blown diagnosis and missing-load-voltage diagnosis.