6AG1321-7RD00-4AB0

Siemens 6AG1321-7RD00-4AB0 SIPLUS S7-300 digital input module with 4 NAMUR inputs, 24 V supply, diagnostics and hazardous-area signals. Request a model-specific quote.

Product Code
6AG1321-7RD00-4AB0
Dimensions
13 × 15 × 5 cm
Weight
0.317 kg
Lifecycle
Product cancellation
Availability
in stock
Lead Time
Confirmed with quotation
Product Attachment
Download Datasheet
Request Current Quote

Current status: in stock. Price, condition, lead time and warranty are confirmed in the quotation.

Product Overview

Technical Summary

Parameter Value
Module type SIPLUS S7-300 digital input module
Digital inputs 4
NAMUR inputs 4
Rated load voltage L+ 24 V DC
Input voltage 8.2 V DC; from internal power circuit supply
NAMUR signal 0 0.35 mA min. to 1.2 mA max.
NAMUR signal 1 2.1 mA min. to 7 mA max.
Input frequency 2 kHz max. with a time delay of 0.1 ms
Diagnostics Yes

Applications

  1. Hazardous-area NAMUR signal acquisition: Acquires signals from the hazardous area through 4 NAMUR digital inputs.

Key Features

  1. 4 NAMUR digital inputs: Provides 4 digital inputs and 4 NAMUR inputs for signals from the hazardous area.
  2. Input signal ranges: NAMUR signal 0: 0.35 mA min. to 1.2 mA max.; signal 1: 2.1 mA min. to 7 mA max.
  3. 24 V DC supply: Rated load voltage L+ is 24 V DC with reverse polarity protection.
  4. Diagnostics and indicators: Diagnostics are supported with readable diagnostic information, group error SF, digital input status, and channel fault indicators.
  5. Parameterizable input delay: NAMUR inputs support 0.1 / 0.5 / 3 / 15 / 20 ms, plus 0.25 ms preparation time.
  6. Hazardous-area isolation: Digital inputs have potential separation between channels and from the backplane bus and load voltage L+, with values dependent on hazardous-area use.

Frequently Asked Questions

1. How many NAMUR inputs does the 6AG1321-7RD00-4AB0 have?

It has 4 NAMUR inputs and 4 digital inputs.

2. What NAMUR signal ranges does this module support?

Signal 0 is 0.35 mA min. to 1.2 mA max.; signal 1 is 2.1 mA min. to 7 mA max.

3. What supply voltage does the module use?

The rated load voltage L+ is 24 V DC. Input voltage is 8.2 V DC from the internal power circuit supply.

4. What diagnostics are available?

Diagnostics are supported, with readable diagnostic information, group error SF, digital input status, and channel fault indicators.