Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Module type | SIPLUS S7-300 digital input module |
| Digital inputs | 4 |
| NAMUR inputs | 4 |
| Rated load voltage L+ | 24 V DC |
| Input voltage | 8.2 V DC; from internal power circuit supply |
| NAMUR signal 0 | 0.35 mA min. to 1.2 mA max. |
| NAMUR signal 1 | 2.1 mA min. to 7 mA max. |
| Input frequency | 2 kHz max. with a time delay of 0.1 ms |
| Diagnostics | Yes |
Applications
- Hazardous-area NAMUR signal acquisition: Acquires signals from the hazardous area through 4 NAMUR digital inputs.
Key Features
- 4 NAMUR digital inputs: Provides 4 digital inputs and 4 NAMUR inputs for signals from the hazardous area.
- Input signal ranges: NAMUR signal 0: 0.35 mA min. to 1.2 mA max.; signal 1: 2.1 mA min. to 7 mA max.
- 24 V DC supply: Rated load voltage L+ is 24 V DC with reverse polarity protection.
- Diagnostics and indicators: Diagnostics are supported with readable diagnostic information, group error SF, digital input status, and channel fault indicators.
- Parameterizable input delay: NAMUR inputs support 0.1 / 0.5 / 3 / 15 / 20 ms, plus 0.25 ms preparation time.
- Hazardous-area isolation: Digital inputs have potential separation between channels and from the backplane bus and load voltage L+, with values dependent on hazardous-area use.
Frequently Asked Questions
1. How many NAMUR inputs does the 6AG1321-7RD00-4AB0 have?
It has 4 NAMUR inputs and 4 digital inputs.
2. What NAMUR signal ranges does this module support?
Signal 0 is 0.35 mA min. to 1.2 mA max.; signal 1 is 2.1 mA min. to 7 mA max.
3. What supply voltage does the module use?
The rated load voltage L+ is 24 V DC. Input voltage is 8.2 V DC from the internal power circuit supply.
4. What diagnostics are available?
Diagnostics are supported, with readable diagnostic information, group error SF, digital input status, and channel fault indicators.