6AG1321-7BH01-2AB0

Siemens 6AG1321-7BH01-2AB0 SIPLUS S7-300 digital input module with 16 isolated DI, 24 V DC, diagnostics, interrupts, and 20-pole connection. Request a model-specific quote.

Product Code
6AG1321-7BH01-2AB0
Dimensions
13 × 15 × 5 cm
Weight
0.249 kg
Lifecycle
Product cancellation
Availability
in stock
Lead Time
Confirmed with quotation
Product Attachment
Download Datasheet
Request Current Quote

Current status: in stock. Price, condition, lead time and warranty are confirmed in the quotation.

Product Overview

Technical Summary

Parameter Value
Digital inputs 16
Input voltage, rated 24 V DC
Input voltage, signal 0 -30 to +5 V
Input voltage, signal 1 13 to 30V
Load voltage L+, permissible range 20.4 V to 28.8 V
Connection 1x 20-pole
Diagnostics Parameterizable diagnostics, diagnostic alarms, hardware interrupts, and wire-break detection to I< 1 mA
Isolation Between digital inputs and backplane bus: optocoupler
Isochronous mode Yes
Power loss, typ. 4 W

Applications

  1. Digital signal acquisition: Acquires signals through 16 digital inputs with 24 V DC input characteristics.

Key Features

  1. Digital inputs: 16 digital inputs with a 24 V DC rated input voltage.
  2. Input signal ranges: Signal 0: -30 to +5 V; signal 1: 13 to 30V.
  3. Connection and supply: 1x 20-pole connection; load voltage L+ rated at 24 V, with a permissible range of 20.4 V to 28.8 V.
  4. Diagnostics and interrupts: Parameterizable diagnostics, diagnostic alarms, hardware interrupts, readable diagnostic information, and wire-break detection to I< 1 mA.
  5. Isolation and protection: Digital inputs are isolated from the backplane bus by an optocoupler; reverse polarity protection is provided for load voltage L+.
  6. Installation and mode: Supports isochronous mode; 16 inputs are supported for horizontal installation up to 60 °C and vertical installation up to 40 °C.

Frequently Asked Questions

1. How many digital inputs does 6AG1321-7BH01-2AB0 have?

It has 16 digital inputs.

2. What input voltage does this module use?

The rated input voltage is 24 V DC. Signal 0 is -30 to +5 V, and signal 1 is 13 to 30V.

3. What diagnostics and interrupt functions are available?

It has parameterizable diagnostics, diagnostic alarms, hardware interrupts, readable diagnostic information, and wire-break detection to I< 1 mA.

4. What connection and load-voltage range does it have?

It has a 1x 20-pole connection. Load voltage L+ is rated at 24 V, with a permissible range of 20.4 V to 28.8 V.

5. What installation conditions should be verified before inquiry?

The module supports 16 inputs for horizontal installation up to 60 °C and vertical installation up to 40 °C.

Send Inquiry