Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Product type | DQ 8×24 VDC/0.5 A ST |
| Digital outputs | 8 source outputs (PNP, current-sourcing) |
| Rated supply voltage | 24 V DC |
| Permissible supply voltage | 19.2 V to 28.8 V DC |
| Rated output current | 0.5 A per output |
| Maximum module current | 4 A |
| Output switching frequency | 100 Hz with resistive load; 2 Hz with inductive load; 10 Hz on lamp load |
| BaseUnit | BU type A0 |
| Color code | CC02 |
| Isolation | 750 V DC (type test) and according to EN 50155 (routine test) |
Applications
- Digital input control: The outputs can control a digital input.
- Redundant load control: Two outputs can be switched in parallel for redundant control of a load.
Key Features
- Digital output channels: 8 parameterizable source outputs (PNP, current-sourcing); current-sinking is not supported.
- Output rating: 0.5 A rated current per output and 4 A maximum per module; above +60 °C, maximum total current is 1.0 A.
- Supply and protection: 24 V DC rated supply with a permissible range of 19.2 V to 28.8 V, reverse polarity protection, and short-circuit protection.
- Diagnostics: Channel-by-channel wire-break and short-circuit diagnostics, supply-voltage monitoring, group error, diagnostic alarms, and substitute values.
- Connections and installation: Supports BU type A0 and shielded cable lengths up to 1 000 m or unshielded cable lengths up to 600 m.
Frequently Asked Questions
1. What type of outputs does 6AG2132-6BF00-4CA0 have?
It has 8 parameterizable source outputs (PNP, current-sourcing). Current-sinking is not supported.
2. What supply voltage does this module require?
The rated supply voltage is 24 V DC, with a permissible range of 19.2 V to 28.8 V DC.
3. What current can the outputs handle?
The rated current is 0.5 A per output and the maximum current is 4 A per module. Above +60 °C, the maximum total current is 1.0 A.
4. Which diagnostics are available?
The module has channel-by-channel wire-break and short-circuit diagnostics, supply-voltage monitoring, group error indication, diagnostic alarms, and substitute values.