Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Product type | IM 153-2 HF |
| Module capacity | Up to 12 modules per DP device interface |
| PROFIBUS DP protocol | PROFIBUS DP to EN 50170 |
| Transmission interface | RS 485 |
| Transmission rate, max. | 12 Mbit/s |
| Rated supply voltage | 24 V DC |
| Permissible supply voltage | 20.4 V to 28.8 V DC |
| Time-stamp accuracy | 1 ms at up to 8 modules; 10 ms at up to 12 modules |
| Stampable digital inputs, max. | 128; max. 32 signals/slot |
| Connection | 9-pin sub D socket |
| Protection | IP20 |
Applications
- PROFIBUS DP communication: Communicates through PROFIBUS DP to EN 50170 using RS 485, with SYNC, FREEZE and direct data exchange capabilities.
- Digital input time stamping: Records signal changes on digital inputs with rising or falling-edge time stamping.
- STEP 7 configuration: Can be configured with STEP 7 / COM PROFIBUS / non-Siemens tools via the GSD file.
Key Features
- ET 200M interface module: Product type designation: IM 153-2 HF; the module is based on 6ES7153-2BA10-0XB0 and has conformal coating.
- Module capacity: Supports up to 12 modules per DP device interface, with redundancy capability.
- PROFIBUS DP interface: Uses RS 485 with a maximum transmission rate of 12 Mbit/s and automatic transmission-rate detection; connection: 9-pin sub D socket.
- Time stamping: Time-stamp accuracy is 1 ms with up to 8 modules and 10 ms with up to 12 modules; up to 128 stampable digital inputs are supported, with a maximum of 32 signals/slot.
- Supply and current: Rated supply voltage is 24 V DC, with a permissible range of 20.4 V to 28.8 V; maximum current consumption is 650 mA with 24 V DC supply.
- Protection and dimensions: IP20 protection; dimensions are 40 mm wide, 125 mm high and 117 mm deep, with an approximate weight of 360 g.
Frequently Asked Questions
1. What is the product type of Siemens 6AG1153-2BA10-7XB0?
It has the product type designation IM 153-2 HF and is based on 6ES7153-2BA10-0XB0.
2. How many modules can the IM 153-2 HF support?
It supports up to 12 modules per DP device interface.
3. What PROFIBUS DP interface and connection does it use?
It uses an RS 485 interface with a maximum transmission rate of 12 Mbit/s and a 9-pin sub D socket.
4. What supply voltage does this module require?
Its rated supply voltage is 24 V DC, with a permissible range of 20.4 V to 28.8 V DC.