Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Rated load voltage | 24 to 48 V DC |
| Current-carrying capacity, max. | 10 A up to 60 °C |
| Input current, max. | 12 mA from load voltage L+ without load |
| Power loss, typ. | 0.5 W |
| Reverse polarity protection | Yes |
| Missing load voltage diagnosis | Yes |
| PWR diagnostic indication | Yes, green |
| SF group error indication | Yes, red |
| Isolation test voltage | 500 V DC |
Key Features
- Rated load voltage: 24 to 48 V DC.
- Current-carrying capacity: 10 A max. up to 60 °C.
- Input current: 12 mA max. from load voltage L+ without load.
- Protection: Reverse polarity protection: Yes. Short-circuit protection: No; external protection is required, e.g. an automatic circuit breaker with tripping characteristic B or C.
- Diagnostics: Missing load voltage diagnosis is available. LEDs indicate rated load voltage PWR (green) and group error SF (red).
- Isolation and parameters: Potential separation is provided between rated load voltage and backplane bus, and between power modules. Isolation is tested with 500 V DC. The parameter remark is 3 byte; missing load voltage can be disabled or enabled.
Frequently Asked Questions
1. What rated load voltage does the 6AG1138-4CA50-2AB0 use?
Its rated load voltage is 24 to 48 V DC.
2. What current-carrying capacity is specified?
The maximum current-carrying capacity is 10 A up to 60 °C.
3. Does the module provide diagnostics?
Yes. It diagnoses missing load voltage and has PWR (green) and SF (red) diagnostic LEDs.
4. Is short-circuit protection included?
No. External protection is required, such as an automatic circuit breaker with tripping characteristic B or C.
5. What should be verified before requesting a quote?
Verify the 24 to 48 V DC load-voltage requirement, the 10 A capacity up to 60 °C, external short-circuit protection, and the required diagnostic indications.