Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Analog output channels | 2 |
| Supported current ranges | -20 mA to +20 mA; 4 mA to 20 mA |
| Resolution with overrange | 14 bit including sign; 4 mA to 20 mA: 13 bit, ±20 mA: 14 bit |
| Cycle time, all channels, max. | 1.5 ms |
| Rated load voltage | 24 V DC; from power module |
| Load impedance with current outputs, max. | 500 Ω |
| Wire-break diagnosis | Yes |
| Group-error diagnosis | Yes; red SF LED |
| Potential separation | Between channels and backplane bus; between channels and load voltage L+ |
| Ambient temperature during operation | -25 °C to 70 °C |
Applications
- Current output control: Controls actuators through two-wire current outputs.
Key Features
- Analog outputs: 2 analog current outputs support -20 mA to +20 mA and 4 mA to 20 mA output ranges.
- Resolution: Resolution with overrange is 14 bit including sign; 4 mA to 20 mA provides 13 bit and ±20 mA provides 14 bit.
- Output timing: Maximum cycle time for all channels is 1.5 ms; settling time is 0.1 ms for resistive loads and 0.5 ms for capacitive or inductive loads.
- Diagnostics: Wire-break and group-error diagnostics are available, with a red group-error SF LED.
- Supply and isolation: Rated load voltage is 24 V DC from the power module. The analog outputs are separated from the backplane bus and load voltage L+, but not between channels.
- Connection and dimensions: Two-wire connection is supported for current-output actuators; four-wire connection is not. Dimensions are 15 mm wide, 81 mm high, and 52 mm deep.
Frequently Asked Questions
1. How many analog outputs does the 6AG1135-4GB01-2AB0 have?
It has 2 analog current outputs.
2. Which current ranges does this module support?
It supports -20 mA to +20 mA and 4 mA to 20 mA output ranges.
3. What resolution is available for the current outputs?
Resolution with overrange is 14 bit including sign; 4 mA to 20 mA provides 13 bit and ±20 mA provides 14 bit.
4. What diagnostics are available?
Wire-break and group-error diagnostics are available, and group error is indicated by a red SF LED.
5. Which actuator connection should be verified before inquiry?
Two-wire connection for current-output actuators is supported; four-wire connection is not.