6AG1135-4GB01-2AB0

Siemens 6AG1135-4GB01-2AB0 SIPLUS ET 200S analog output module with 2 current outputs, 4 mA to 20 mA and -20 mA to +20 mA ranges. Request a model-specific quote.

Product Code
6AG1135-4GB01-2AB0
Dimensions
9 × 6 × 2 cm
Weight
0.045 kg
Lifecycle
Product cancellation
Availability
in stock
Lead Time
Confirmed with quotation
Product Attachment
Download Datasheet
Request Current Quote

Current status: in stock. Price, condition, lead time and warranty are confirmed in the quotation.

Product Overview

Technical Summary

Parameter Value
Analog output channels 2
Supported current ranges -20 mA to +20 mA; 4 mA to 20 mA
Resolution with overrange 14 bit including sign; 4 mA to 20 mA: 13 bit, ±20 mA: 14 bit
Cycle time, all channels, max. 1.5 ms
Rated load voltage 24 V DC; from power module
Load impedance with current outputs, max. 500 Ω
Wire-break diagnosis Yes
Group-error diagnosis Yes; red SF LED
Potential separation Between channels and backplane bus; between channels and load voltage L+
Ambient temperature during operation -25 °C to 70 °C

Applications

  1. Current output control: Controls actuators through two-wire current outputs.

Key Features

  1. Analog outputs: 2 analog current outputs support -20 mA to +20 mA and 4 mA to 20 mA output ranges.
  2. Resolution: Resolution with overrange is 14 bit including sign; 4 mA to 20 mA provides 13 bit and ±20 mA provides 14 bit.
  3. Output timing: Maximum cycle time for all channels is 1.5 ms; settling time is 0.1 ms for resistive loads and 0.5 ms for capacitive or inductive loads.
  4. Diagnostics: Wire-break and group-error diagnostics are available, with a red group-error SF LED.
  5. Supply and isolation: Rated load voltage is 24 V DC from the power module. The analog outputs are separated from the backplane bus and load voltage L+, but not between channels.
  6. Connection and dimensions: Two-wire connection is supported for current-output actuators; four-wire connection is not. Dimensions are 15 mm wide, 81 mm high, and 52 mm deep.

Frequently Asked Questions

1. How many analog outputs does the 6AG1135-4GB01-2AB0 have?

It has 2 analog current outputs.

2. Which current ranges does this module support?

It supports -20 mA to +20 mA and 4 mA to 20 mA output ranges.

3. What resolution is available for the current outputs?

Resolution with overrange is 14 bit including sign; 4 mA to 20 mA provides 13 bit and ±20 mA provides 14 bit.

4. What diagnostics are available?

Wire-break and group-error diagnostics are available, and group error is indicated by a red SF LED.

5. Which actuator connection should be verified before inquiry?

Two-wire connection for current-output actuators is supported; four-wire connection is not.