Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Analog input channels | 2 |
| Supported resistance thermometer types | Cu 10, Ni 100, Ni 1000, Ni 120, Ni 200, Ni 500, Pt 100, Pt 1000, Pt 200, Pt 500 |
| Rated resistor input ranges | 0 to 150 ohms; 0 to 300 ohms; 0 to 600 ohms; 0 to 3000 ohms |
| Rated load voltage L+ | 24 V; From power module |
| Maximum input current from load voltage L+ | 30 mA; without load |
| Maximum input current from backplane bus | 10 mA; 3.3 V DC |
| Resolution with overrange | 16 bit max.; specified RTDs: 15 bit + sign; resistor ranges: 15 bit; PTC: 1 bit |
| Measurement principle | integrating (Sigma-Delta) |
| Signal-encoder connections | Two-wire, three-wire with internal line-resistance compensation, and four-wire |
| Isolation test voltage | 500 V DC |
Applications
- Resistance measurement: Measures resistance using two-wire, three-wire, or four-wire signal-encoder connections.
- Temperature measurement: Measures temperature with supported resistance thermometers including Cu 10, Ni, and Pt types.
- Input diagnostics: Provides wire-break, group-error, and overflow/underflow diagnostics for the analog inputs.
Key Features
- Analog inputs: 2 analog inputs support resistance thermometers including Cu 10, Ni 100, Ni 1000, Ni 120, Ni 200, Ni 500, Pt 100, Pt 1000, Pt 200, and Pt 500.
- Resistor input ranges: Rated resistor ranges include 0 to 150 ohms, 0 to 300 ohms, 0 to 600 ohms, and 0 to 3000 ohms.
- Supply and current: Load voltage L+ is 24 V rated, from the power module. Input current is max. 30 mA from load voltage L+ without load and max. 10 mA from the 3.3 V DC backplane bus.
- Measurement and resolution: The measurement principle is integrating (Sigma-Delta). Resolution with overrange is max. 16 bit; for specified RTDs it is 15 bit + sign, for resistor ranges it is 15 bit, and for PTC it is 1 bit.
- Diagnostics and isolation: Diagnostics include wire break, group error, and overflow/underflow. The analog inputs are isolated from the backplane bus and load voltage L+; isolation is tested with 500 V DC.
- Connection and coating: Two-wire, three-wire with internal line-resistance compensation, and four-wire resistance measurement are supported. Shielded cable length is max. 200 m, and the module has conformal coating.
Frequently Asked Questions
1. How many analog inputs does 6AG1134-4NB51-2AB0 have?
It has 2 analog inputs.
2. Which resistance ranges are supported?
The rated ranges are 0 to 150 ohms, 0 to 300 ohms, 0 to 600 ohms, and 0 to 3000 ohms.
3. Which resistance-thermometer types are supported?
Supported types are Cu 10, Ni 100, Ni 1000, Ni 120, Ni 200, Ni 500, Pt 100, Pt 1000, Pt 200, and Pt 500.
4. What diagnostics are available?
Diagnostics include wire break, group error, and overflow/underflow, with a red group-error SF LED indication.