Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Analog input channels | 2 |
| Rated input ranges | 1 V to 5 V; -10 V to +10 V; -5 V to +5 V |
| Resolution with overrange | 16 bit including sign; 0 to 5 V: 15 bit, ±10 V: 16 bit, ±5 V: 16 bit |
| Maximum cycle time | 0.5 ms for all channels; 0.5 ms for 2 channels without noise suppression |
| Rated load voltage L+ | 24 V DC |
| Input resistance | 800 kΩ for 1 V to 5 V, -10 V to +10 V, and -5 V to +5 V |
| Power loss, typical | 0.85 W |
| Diagnostics | Hardware interrupt; wire break for 1 to 5 V only; group error; overflow/underflow |
| Isolation | Between analog inputs and backplane bus; between analog inputs and load voltage L+ |
| Conformal coating temperature range | -25…+60 °C |
Applications
- Voltage measurement: Supports voltage measurement through the 1 V to 5 V, -10 V to +10 V, and -5 V to +5 V input ranges.
- Signal encoder connection: Provides connection for signal encoders for voltage measurement.
Key Features
- Analog voltage inputs: 2 analog inputs support 1 V to 5 V, -10 V to +10 V, and -5 V to +5 V rated input ranges.
- Resolution: Resolution with overrange is 16 bit including sign; 0 to 5 V uses 15 bit, while ±10 V and ±5 V use 16 bit.
- Cycle time: Maximum cycle time for all channels is 0.5 ms; this is 0.5 ms for 2 channels without noise suppression.
- Diagnostics: The module has hardware interrupt, wire-break detection for the 1 to 5 V measuring range, group error, overflow/underflow, and a red group error SF LED.
- Supply and isolation: Rated load voltage L+ is 24 V DC with reverse polarity protection. The analog inputs are isolated from the backplane bus and load voltage L+.
- Conformal coating and size: SIPLUS design with conformal coating and -25…+60 °C; module width is 15 mm.
Frequently Asked Questions
1. How many analog inputs does the 6AG1134-4LB02-2AB0 have?
It has 2 analog inputs.
2. Which voltage input ranges are supported?
The supported rated voltage ranges are 1 V to 5 V, -10 V to +10 V, and -5 V to +5 V.
3. What resolution does the module provide?
Resolution with overrange is 16 bit including sign; 0 to 5 V uses 15 bit, while ±10 V and ±5 V use 16 bit.
4. What diagnostics are available?
It has hardware interrupt, wire-break detection for the 1 to 5 V measuring range, group error, overflow/underflow, and a red group error SF LED.
5. What supply and isolation data should be checked before inquiry?
Rated load voltage L+ is 24 V DC with reverse polarity protection. The analog inputs are isolated from the backplane bus and load voltage L+.