6AG1134-4LB02-2AB0

Siemens 6AG1134-4LB02-2AB0 SIPLUS ET 200S module with 2 analog voltage inputs, +/-10 V to 1 V to 5 V ranges, 16-bit resolution, and 24 V supply. Request a model-specific quote.

Product Code
6AG1134-4LB02-2AB0
Dimensions
9 × 6.2 × 2.3 cm
Weight
0.056 kg
Lifecycle
Product cancellation
Availability
in stock
Lead Time
Confirmed with quotation
Product Attachment
Download Datasheet
Request Current Quote

Current status: in stock. Price, condition, lead time and warranty are confirmed in the quotation.

Product Overview

Technical Summary

Parameter Value
Analog input channels 2
Rated input ranges 1 V to 5 V; -10 V to +10 V; -5 V to +5 V
Resolution with overrange 16 bit including sign; 0 to 5 V: 15 bit, ±10 V: 16 bit, ±5 V: 16 bit
Maximum cycle time 0.5 ms for all channels; 0.5 ms for 2 channels without noise suppression
Rated load voltage L+ 24 V DC
Input resistance 800 kΩ for 1 V to 5 V, -10 V to +10 V, and -5 V to +5 V
Power loss, typical 0.85 W
Diagnostics Hardware interrupt; wire break for 1 to 5 V only; group error; overflow/underflow
Isolation Between analog inputs and backplane bus; between analog inputs and load voltage L+
Conformal coating temperature range -25…+60 °C

Applications

  1. Voltage measurement: Supports voltage measurement through the 1 V to 5 V, -10 V to +10 V, and -5 V to +5 V input ranges.
  2. Signal encoder connection: Provides connection for signal encoders for voltage measurement.

Key Features

  1. Analog voltage inputs: 2 analog inputs support 1 V to 5 V, -10 V to +10 V, and -5 V to +5 V rated input ranges.
  2. Resolution: Resolution with overrange is 16 bit including sign; 0 to 5 V uses 15 bit, while ±10 V and ±5 V use 16 bit.
  3. Cycle time: Maximum cycle time for all channels is 0.5 ms; this is 0.5 ms for 2 channels without noise suppression.
  4. Diagnostics: The module has hardware interrupt, wire-break detection for the 1 to 5 V measuring range, group error, overflow/underflow, and a red group error SF LED.
  5. Supply and isolation: Rated load voltage L+ is 24 V DC with reverse polarity protection. The analog inputs are isolated from the backplane bus and load voltage L+.
  6. Conformal coating and size: SIPLUS design with conformal coating and -25…+60 °C; module width is 15 mm.

Frequently Asked Questions

1. How many analog inputs does the 6AG1134-4LB02-2AB0 have?

It has 2 analog inputs.

2. Which voltage input ranges are supported?

The supported rated voltage ranges are 1 V to 5 V, -10 V to +10 V, and -5 V to +5 V.

3. What resolution does the module provide?

Resolution with overrange is 16 bit including sign; 0 to 5 V uses 15 bit, while ±10 V and ±5 V use 16 bit.

4. What diagnostics are available?

It has hardware interrupt, wire-break detection for the 1 to 5 V measuring range, group error, overflow/underflow, and a red group error SF LED.

5. What supply and isolation data should be checked before inquiry?

Rated load voltage L+ is 24 V DC with reverse polarity protection. The analog inputs are isolated from the backplane bus and load voltage L+.