Technical Summary
| Parameter | Value |
|---|---|
| Module type | SIPLUS ET 200S EM 2AI high speed |
| Analog inputs | 2 |
| Input ranges | 0 to 20 mA; 4 mA to 20 mA |
| Cycle time, all channels, max. | 0.25 ms |
| Resolution with overrange, including sign, max. | 16 bit |
| Load voltage L+, rated value (DC) | 24 V |
| Wire-break diagnosis | At 4 mA to 20 mA |
Applications
- Current measurement: The module supports current measurement as a 2-wire transducer.
Key Features
- 2 analog inputs: The module has 2 analog inputs with a maximum cycle time of 0.25 ms for all channels.
- Current input ranges: Supported rated input ranges are 0 to 20 mA and 4 mA to 20 mA; input resistance for 0 to 20 mA is 106 Ω.
- High-speed resolution: Resolution with overrange, including sign, is up to 16 bit. Isochronous mode is supported.
- Supply and protection: Rated load voltage L+ is 24 V DC. The load voltage has short-circuit and reverse polarity protection, and transmitter power supply is short-circuit proof.
- Diagnostics and isolation: The module supports hardware interrupts, wire-break diagnosis at 4 mA to 20 mA, group error, overflow/underflow, and group-error SF red LED indication. The analog inputs are isolated from the backplane bus and load voltage L+, but not from each other.
- Conformal coating and connection: The module has conformal coating, supports shielded cables up to 200 m, and has a typical power loss of 2.5 W.
Frequently Asked Questions
1. How many analog inputs does the 6AG1134-4GB52-2AB0 have?
It has 2 analog inputs, with a maximum cycle time of 0.25 ms for all channels.
2. Which current input ranges does the module support?
It supports 0 to 20 mA and 4 mA to 20 mA rated input ranges.
3. What resolution does the analog module provide?
Resolution with overrange, including sign, is up to 16 bit.
4. What diagnostics are available?
It supports hardware interrupts, wire-break diagnosis at 4 mA to 20 mA, group error, overflow/underflow, and group-error SF red LED indication.
5. Is the module isolated between its analog inputs?
No. The analog inputs are not isolated from each other, but they are isolated from the backplane bus and load voltage L+.