| Parameter | Value |
|---|---|
| Module type | DQ 8×24 V DC/0.5 A HF |
| Digital outputs | 8 |
| Output type | Source output (PNP, current-sourcing) |
| Rated supply voltage | 24 V DC |
| Permissible supply voltage | 19.2 V to 28.8 V DC |
| Rated output current per channel | 0.5 A |
| Maximum current per module | 4 A |
| Maximum switching frequency | 100 Hz with resistive load; 2 Hz with inductive load; 10 Hz on lamp load |
| Diagnostics | Wire break and short-circuit, channel by channel; supply voltage; group error |
| BaseUnit | BU type A0 |
| Isolation | Between channels and backplane bus: yes; between channels: no |
| Product lifecycle | Product cancellation |
Applications
- Digital output control: Controls digital outputs using 8 parameterizable source outputs.
- Digital input control: Supports controlling a digital input.
Key Features
- Digital outputs: 8 parameterizable source outputs (PNP, current-sourcing); current-sinking is not supported.
- Output ratings: Rated output voltage: 24 V DC; rated output current per channel: 0.5 A; maximum current per module: 4 A.
- Supply and protection: Rated supply voltage: 24 V DC, permissible range 19.2 V to 28.8 V; reverse polarity and short-circuit protection are provided.
- Diagnostics: Channel-by-channel wire-break and short-circuit diagnostics, supply-voltage monitoring, diagnostic alarm, group error, and PWR, channel-status, and DIAG LEDs.
- Connection and installation: Suitable for BU type A0, with color code CC02; maximum cable length is 1 000 m shielded or 600 m unshielded.
- Configuration and coating: Based on 6ES7132-6BF00-0CA0, with conformal coating, firmware V1.2, and FW update possible.
Frequently Asked Questions
1. How many outputs does Siemens 6AG1132-6BF00-7CA0 have?
It has 8 parameterizable digital source outputs.
2. What supply voltage and output current does this module use?
The rated supply voltage is 24 V DC, with a permissible range of 19.2 V to 28.8 V DC. The rated output current is 0.5 A per channel, and the maximum current per module is 4 A.
3. What diagnostics are available?
It provides channel-by-channel wire-break and short-circuit diagnostics, supply-voltage monitoring, diagnostic alarms, group error information, and PWR, channel-status, and DIAG LEDs.