Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Product type | DQ 4×24 V DC/2 A ST |
| Digital output channels | 4 |
| Output type | Source output (PNP, current-sourcing) |
| Rated supply voltage | 24 V DC |
| Permissible supply voltage | 19.2 V to 28.8 V DC |
| Rated output current | 2 A |
| Short-circuit protection | Yes |
| BaseUnit | BU type A0 |
Applications
- Digital output control: Controls digital loads through 4 source outputs.
- Redundant load control: Supports parallel switching of two outputs for redundant control of a load.
Key Features
- Digital outputs: 4 source outputs (PNP, current-sourcing) with 2 A rated output current.
- Supply voltage: Rated supply voltage: 24 V DC; permissible range: 19.2 V to 28.8 V DC.
- Protection and diagnostics: Short-circuit protection, channel diagnostics, supply-voltage monitoring, wire-break detection, short-circuit detection, and group error indication.
- Output switching capacity: Maximum switching capacity is 2 A with resistive load and 10 W with lamp load.
- Installation and connection: Suitable for BU type A0; maximum cable length is 1 000 m shielded or 200 m unshielded.
- Environmental design: Conformal coating with a temperature range of -40…+70 °C.
Frequently Asked Questions
1. What output type and channel count does the 6AG1132-6BD20-7BA0 have?
It has 4 source outputs (PNP, current-sourcing).
2. What supply voltage does this module require?
The rated supply voltage is 24 V DC, with a permissible range of 19.2 V to 28.8 V DC.
3. What diagnostics and protection are provided?
It has short-circuit protection, channel diagnostics, supply-voltage monitoring, wire-break detection, short-circuit detection, and group error indication.
4. Which BaseUnit is suitable for this module?
It is suitable for BU type A0.