Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Module type | SIPLUS OLM/G11-1300 V4.0 optical link module |
| RS-485 interface | 1 |
| Optical interface | 1 BFOC port for fiber-optic cable |
| PROFIBUS transfer rate | 9.6 kbit/s … 12 Mbit/s |
| Rated supply | 24 V DC |
| Mounting | 35 mm DIN-rail mounting; wall mounting |
Applications
- Optical network coupling: Provides optical link communication between an RS-485 interface and a glass fiber-optic cable interface.
Key Features
- Optical link function: SIPLUS OLM/G11-1300 V4.0 optical link module with 1 RS-485 and 1 glass fiber-optic cable interface using 2 BFOC sockets.
- PROFIBUS transfer rate: Transfer rate with PROFIBUS: 9.6 kbit/s … 12 Mbit/s; with PROFIBUS PA: 45.45 kbit/s.
- Electrical connections: 1 9-pin Sub-D socket for network components or terminal equipment, 1 2-pole terminal block for the measuring device, and 1 5-pole terminal block for power supply and signaling contact.
- Supply and signaling: 24 V DC rated supply; supply range 18.8 … 28.8 V DC; maximum consumed current 0.2 A at 24 V DC; signaling contact operating voltage 24 V DC and maximum operational current 0.1 A.
- Fiber-optic transmission: 1 BFOC optical interface, 1310 nm single-mode wavelength, and maximum wire length 15 km for glass FOC with 10/125 μm or 9/125 μm at 0.5 dB/km.
- Installation and protection: 35 mm DIN-rail mounting and wall mounting; compact design measuring 39.5 mm wide, 112 mm high, and 74.5 mm deep; protection class IP40 and conformal coating, class A.
Frequently Asked Questions
1. What communication interfaces does the 6AG1503-2CC00-2AA0 have?
It has 1 RS-485 interface and 1 BFOC optical interface for fiber-optic cable.
2. What PROFIBUS transfer rates does this module support?
It supports 9.6 kbit/s … 12 Mbit/s with PROFIBUS and 45.45 kbit/s with PROFIBUS PA.
3. What connectors are provided?
The module has a 9-pin Sub-D socket, a 2-pole terminal block, and a 5-pole terminal block for power supply and signaling contact.
4. What supply does the module require?
The rated supply is 24 V DC, with a supply range of 18.8 … 28.8 V DC and maximum consumed current of 0.2 A at 24 V DC.
5. How can the module be mounted?
It supports 35 mm DIN-rail mounting and wall mounting.