Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Module type | Logic module with conformal coating |
| Digital inputs | 8 |
| Digital outputs | 4 relay outputs |
| Supply | 115 V AC/DC and 230 V AC/DC |
| Permissible supply range | 100 V to 253 V |
| Permissible line frequency | 47 Hz to 63 Hz |
| Communication | Ethernet |
| Installation | 35 mm DIN rail, 4 spacing units wide |
| Memory | 400 blocks |
| Operating temperature | -40 °C to 70 °C; startup at -25 °C |
| Protection | Conformal coating, EN 61086 Class 2 |
Key Features
- Digital I/O: 8 digital inputs and 4 digital relay outputs; outputs have no short-circuit protection, so external fusing is necessary.
- Supply and line frequency: 115 V AC/DC and 230 V AC/DC rated values; permissible supply range is 100 V to 253 V, with a permissible line frequency range of 47 Hz to 63 Hz.
- Communication and web functions: Ethernet, integrated web server, data log, and user-defined web pages.
- Memory and expansion: Memory: 400 blocks. The logic module is modularly expandable and supports a standard microSD card for LOGO! Soft Comfort V8.3 or higher; older projects are executable.
- Installation and dimensions: Mounting: on 35 mm DIN rail, 4 spacing units wide. Dimensions: 71.5 mm width, 90 mm height, and 60 mm depth.
- Environmental protection: Conformal coating according to EN 61086 Class 2 for high reliability; protection against fouling according to EN 60664-3 Type 1.
Frequently Asked Questions
1. How many digital I/O points does the 6AG1052-2FB08-7BA1 have?
It has 8 digital inputs and 4 digital relay outputs.
2. What supply values are supported?
The rated values are 115 V AC/DC and 230 V AC/DC. The permissible supply range is 100 V to 253 V.
3. Does this logic module include Ethernet?
Yes. It has Ethernet, an integrated web server, data log, and user-defined web pages.
4. How is the module mounted?
It mounts on a 35 mm DIN rail and is 4 spacing units wide.
5. Does the module have a display or short-circuit protection for its outputs?
It is without a display, and the digital outputs have no short-circuit protection; external fusing is necessary.