6ES7421-1EL00-0AA0

Siemens 6ES7421-1EL00-0AA0 SIMATIC S7-400 SM 421 digital input module with 32 isolated AC/DC inputs, 120 V rated input and LED status indication. Request a model-specific quote.

Product Code
6ES7421-1EL00-0AA0
Dimensions
30.2 × 23.5 × 3.7 cm
Weight
0.773 kg
Lifecycle
Announcement of product phase-out
Availability
in stock
Lead Time
Confirmed with quotation
Product Attachment
Download Datasheet
Request Current Quote

Current status: in stock. Price, condition, lead time and warranty are confirmed in the quotation.

Product Overview

Technical Summary

Parameter Value
Digital input channels 32
Simultaneously controllable inputs 32
Input voltage type AC/DC
Rated input voltage 120 V; 47 … 63 Hz
Signal "0" input voltage 0 to 20 V UC
Signal "1" input voltage 79 to 132 V AC; 80 to 132 V DC
Input characteristic Type 1
Channel isolation grouping 8
Backplane bus current 200 mA max. from 5 V DC
Typical power loss 6.5 W
Input status indication Green LED

Applications

  1. Digital signal acquisition: Acquires 120 V AC/DC digital input signals through 32 isolated digital input channels.

Key Features

  1. Digital input channels: 32 isolated digital inputs, with 32 inputs simultaneously controllable.
  2. Input voltage: AC/DC input voltage with a rated value of 120 V; 47 … 63 Hz.
  3. Input signal levels: Signal "0": 0 to 20 V UC; signal "1": 79 to 132 V AC or 80 to 132 V DC.
  4. Electrical isolation: Isolation between channels and between the digital inputs and the backplane bus; channel isolation is arranged in groups of 8.
  5. Diagnostics indication: Green LED status indication is provided for the digital inputs.
  6. Cable and sensor connection: Supports 2-wire sensors with a permissible quiescent current of 1 mA max.; maximum cable length is 1 000 m shielded or 600 m unshielded.

Frequently Asked Questions

1. What type of module is the 6ES7421-1EL00-0AA0?

It is a SIMATIC S7-400 SM 421 digital input module with 32 isolated digital inputs.

2. What input voltage does this module support?

The input voltage type is AC/DC, with a rated value of 120 V at 47 … 63 Hz. Signal "0" is 0 to 20 V UC, while signal "1" is 79 to 132 V AC or 80 to 132 V DC.

3. How many inputs can be controlled simultaneously?

All 32 digital inputs can be controlled simultaneously.

4. Does it support 2-wire sensors?

Yes. A 2-wire sensor is supported with a permissible quiescent current of 1 mA max.

Send Inquiry