Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Product type | AQ 4xU/I |
| Analog output channels | 4 |
| Voltage output ranges | 0 to 10 V; 1 V to 5 V; -10 V to +10 V |
| Current output ranges | 0 to 20 mA; -20 mA to +20 mA; 4 mA to 20 mA |
| Resolution | Up to 16 bit including sign |
| Cycle time | 1 ms maximum, all channels |
| Load voltage | 24 V DC rated; 20.4 V to 28.8 V permissible |
| Connections | 4xM12 |
| Protection | IP65/67 |
| Firmware version | V2.0.x |
Applications
- Analog voltage output: Provides analog voltage output through supported voltage ranges for connected actuators.
- Analog current output: Provides analog current output through supported current ranges for connected actuators.
Key Features
- 4 analog output channels: AQ 4xU/I provides 4 analog outputs.
- Voltage and current ranges: Supported ranges include 0 to 10 V, 1 V to 5 V, -10 V to +10 V, 0 to 20 mA, -20 mA to +20 mA, and 4 mA to 20 mA.
- 16-bit resolution: Resolution with overrange is up to 16 bit including sign.
- M12 connections and IP protection: The module has 4xM12 connections and IP65/67 protection.
- Diagnostics: It provides parameterizable diagnostic alarms, channel status indication with a green LED, and wire-break or short-circuit diagnostics with the stated output-type restrictions.
- 24 V supply: Rated load voltage 1L+ is 24 V DC, with a permissible range of 20.4 V to 28.8 V.
Frequently Asked Questions
1. How many analog outputs does the 6ES7145-5ND00-0BA0 have?
It has 4 analog output channels.
2. Which signal ranges are supported?
Voltage ranges are 0 to 10 V, 1 V to 5 V, and -10 V to +10 V. Current ranges are 0 to 20 mA, -20 mA to +20 mA, and 4 mA to 20 mA.
3. What supply voltage does the module require?
The rated load voltage 1L+ is 24 V DC, with a permissible range of 20.4 V to 28.8 V.
4. What connections and protection does it have?
It has 4xM12 connections and IP65/67 protection.