6ES7322-1BP00-0AA0

Siemens 6ES7322-1BP00-0AA0 SIMATIC S7-300 digital output module with 64 DO, 24 V DC supply, and grouped isolation. Request a model-specific quote.

Product Code
6ES7322-1BP00-0AA0
Dimensions
15.1 × 13.1 × 5.2 cm
Weight
0.312 kg
Lifecycle
Product cancellation
Availability
in stock
Lead Time
Confirmed with quotation
Product Attachment
Download Datasheet

Product Tags

Request Current Quote

Current status: in stock. Price, condition, lead time and warranty are confirmed in the quotation.

Product Overview

Technical Summary

Parameter Value
Digital output count 64
Load voltage 24 V DC rated; permissible range 20.4 V to 28.8 V
Rated output current 0.3 A for signal "1"
Output current permissible range 2.4 mA to 0.36 A for signal "1"
Output delay 550 μs maximum for "0" to "1" and "1" to "0" with resistive load
Switching frequency 100 Hz maximum with resistive load; 0.5 Hz maximum with inductive load; 10 Hz maximum on lamp load
Backplane bus current 100 mA maximum from 5 V DC
Power loss 6 W typical

Applications

  1. Digital input control: The outputs can control a digital input.
  2. Redundant load control: Two outputs can be switched in parallel for redundant control of a load.

Key Features

  1. Digital output capacity: 64 digital outputs with 24 V DC load voltage.
  2. Output current: Rated output current for signal "1": 0.3 A; permissible range: 2.4 mA to 0.36 A.
  3. Grouped isolation: Digital outputs are isolated from the backplane bus by optocouplers in groups of 16; channels are not isolated from each other.
  4. Output protection: Electronic short-circuit protection is provided.
  5. Required connections: Required front connector: cable 6ES7392-4Bxx0-0AA0 or terminal blocks 6ES7392-1xN00-0AA0.
  6. Installation limits: For horizontal installation, maximum total current is 1.6 A up to 40 °C and 1.2 A up to 60 °C; vertical installation allows 1.6 A up to 40 °C.

Frequently Asked Questions

1. How many digital outputs does Siemens 6ES7322-1BP00-0AA0 have?

It has 64 digital outputs.

2. What load voltage and output current does this module use?

The rated load voltage is 24 V DC. The rated output current for signal "1" is 0.3 A, with a permissible range of 2.4 mA to 0.36 A.

3. Are the digital outputs isolated from the backplane bus?

Yes. The digital outputs are isolated from the backplane bus by optocouplers in groups of 16, but the channels are not isolated from each other.

4. Which front connector is required?

A cable 6ES7392-4Bxx0-0AA0 or terminal blocks 6ES7392-1xN00-0AA0 are required.

Send Inquiry