Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Product type | Key Panel KP8 PN LX (1 … 6 mm) |
| Digital inputs | 8; maximum 8 inputs and outputs total |
| Digital outputs | 8; maximum 8 inputs and outputs total |
| PROFINET interfaces | 2; includes switch |
| Supply voltage | 24 V DC; permissible range 20.4 V to 28.8 V |
| Output current per channel | 100 mA maximum |
| Output current per group | 800 mA maximum |
| Mounting | Clamp fastening; horizontal or vertical |
| Front protection | IP64 |
| Rear protection | IP20 |
Applications
- Operator key control: 8 direct keys can be used as S7 input I/O for operator control.
- Digital signal output: 8 DP direct LEDs can be used as S7 output I/O, with adjustable brightness and 5 color modes.
- PROFINET communication: The 2 PROFINET interfaces support PROFINET IO, IRT and MRP for industrial Ethernet communication.
Key Features
- Configurable digital channels: 8 digital inputs and 8 digital outputs share a maximum total of 8 inputs and outputs; the outputs have short-circuit protection.
- Short-stroke operator keys: The panel has 8 short-stroke keys and 8 function keys, with 19 x 19 mm per button for the function keys.
- PROFINET interfaces: 2 PROFINET interfaces with an integrated switch support line and ring construction without an external switch; PROFINET IO and IRT are supported.
- 24 V DC supply: Rated supply is 24 V DC, with a permissible range from 20.4 V to 28.8 V. 24 V can be looped through the connector and is interrupted when pulled.
- Front mounting: Clamp fastening with additional mounting clips supports horizontal, vertical, portrait and landscape mounting. Front mounting uses Torx T20 and Torx T10 screws tightened to 0.2 Nm.
- Protection ratings: The enclosure provides IP64 protection at the front and IP20 protection at the rear.
Frequently Asked Questions
1. How many digital channels does the 6AV2127-1AB00-0LX1 have?
It has 8 digital inputs and 8 digital outputs, with a maximum total of 8 inputs and outputs.
2. Which PROFINET interfaces and protocols are supported?
It has 2 PROFINET interfaces with an integrated switch and supports PROFINET, PROFINET IO, IRT and MRP.
3. What supply voltage does the panel require?
The rated supply is 24 V DC, with a permissible range from 20.4 V to 28.8 V.
4. How is the panel mounted?
It uses clamp fastening with additional mounting clips and supports horizontal, vertical, portrait and landscape mounting.