Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Output power (LO) | 110.00 kW | 150.00 hp |
| Output power (HO) | 90.00 kW | 125.00 hp |
| Input line voltage | 380 … 480 V ±10 % |
| Line frequency | 47 … 63 Hz |
| Maximum output current | 356.00 A |
| Output frequency for vector control | 0 … 200 Hz |
| Output frequency for V/f control | 0 … 550 Hz |
| Degree of protection | IP20 / UL open type |
| Frame size | FSF |
| Built-in braking chopper | Yes |
Key Features
- Power and overload ratings: Rated output power is 110.00 kW | 150.00 hp for LO and 90.00 kW | 125.00 hp for HO. LO supports 150% for 3S, 110% for 57S, and 100% for 240S at -20 … 40 °C; HO supports 200% for 3S, 150% for 57S, and 100% for 240S at -20 … 50 °C.
- Input and output data: Input and output each use 3 AC phases. Input line voltage is 380 … 480 V ±10 % with 47 … 63 Hz line frequency; rated input current is 198.00 A LO or 189.00 A HO.
- Output frequency and current: Rated output current is 205.00 A LO or 178.00 A HO, with 356.00 A maximum output current. Output frequency is 0 … 200 Hz for vector control and 0 … 550 Hz for V/f control.
- Connections and motor cable: Line-side and motor-end connections use M10 bolts with 35.00 … 120.00 mm2 conductors. The DC link uses screw-type terminals for 25.00 … 70.00 mm2 conductors; maximum motor cable length is 300 m shielded or 450 m unshielded.
- Protection and installation: The module has IP20 / UL open type protection, FSF frame size, and dimensions of 708 mm height, 305 mm width, and 357 mm depth. Net weight is 61.00 kg.
- Configuration and delivery details: The module has a built-in braking chopper and no integrated filter. It is supplied without a control unit and panel; approved CU firmware version is V4.7 HF8.
Frequently Asked Questions
1. What output power does 6SL3210-1PE32-1UL0 provide?
It provides 110.00 kW | 150.00 hp at LO and 90.00 kW | 125.00 hp at HO.
2. What input supply does this power module require?
It requires 3 AC, 380 … 480 V ±10 %, at 47 … 63 Hz.
3. What connections and motor cable lengths are supported?
Line-side and motor-end connections use M10 bolts with 35.00 … 120.00 mm2 conductors. Maximum motor cable length is 300 m shielded or 450 m unshielded.
4. What is included or excluded from the configuration?
It has a built-in braking chopper and is without an integrated filter, control unit, and panel.