Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Rated output power (LO) | 90.00 kW | 125.00 hp |
| Rated output power (HO) | 75.00 kW | 100.00 hp |
| Input line voltage | 380 … 480 V ±10 % |
| Input line frequency | 47 … 63 Hz |
| Maximum output current | 290.00 A |
| Output frequency for vector control | 0 … 200 Hz |
| Output frequency for V/f control | 0 … 550 Hz |
| Braking chopper | Built-in |
| Frame size | FSF |
| Degree of protection | IP20 / UL open type |
| Control unit and panel | Without control unit and panel |
Key Features
- Output power and overload: Rated output power: 90.00 kW LO or 75.00 kW HO. The collected data specifies 150% for 3S, 110% for 57S and 100% for 240S at LO; and 200% for 3S, 150% for 57S and 100% for 240S at HO.
- Input and output data: Input: 3 AC, 380 … 480 V ±10 %, 47 … 63 Hz. Output: 3 AC, 400V IEC or 480V NEC, with maximum output current of 290.00 A.
- Output frequency control ranges: Output frequency: 0 … 200 Hz for vector control and 0 … 550 Hz for V/f control. Pulse frequency is 2 kHz.
- Built-in braking chopper: The power module has a built-in braking chopper. The DC link uses screw-type terminals and supports a 25.00 … 70.00 mm2 conductor cross-section.
- Connections and motor cables: Line-side and motor-end connections use M10 bolts with 35.00 … 120.00 mm2 conductors. Maximum motor cable length is 300 m shielded or 450 m unshielded.
- Mounting and protection: Frame size: FSF. Dimensions are 708 mm height, 305 mm width and 357 mm depth. Protection degree: IP20 / UL open type.
Frequently Asked Questions
1. What output power does 6SL3210-1PE31-8UL0 provide?
It provides 90.00 kW | 125.00 hp at LO and 75.00 kW | 100.00 hp at HO.
2. What input supply is specified for this power module?
The input is 3 AC, 380 … 480 V ±10 % at 47 … 63 Hz.
3. What output frequency ranges are available?
The output frequency is 0 … 200 Hz for vector control and 0 … 550 Hz for V/f control.
4. What connections and motor cable lengths does it have?
Line-side and motor-end connections use M10 bolts. The maximum motor cable length is 300 m shielded or 450 m unshielded.
5. What is excluded from this configuration?
It is without an integrated filter, control unit and panel.