Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Product type | SINAMICS G120 PM240-2 power module |
| Input | 3 AC, 380 … 480 V ±10 %, 47 … 63 Hz |
| Rated output power (HO) | 55.00 kW | 75.00 hp |
| Rated output power (LO) | 75.00 kW | 100.00 hp |
| Maximum output current | 220.00 A |
| Output frequency for vector control | 0 … 200 Hz |
| Output frequency for V/f control | 0 … 550 Hz |
| Integrated functions | Class A filter and braking chopper |
| Protection | IP20 / UL open type |
| Frame size | FSF |
Key Features
- Output power and overload: Rated output power is 55.00 kW | 75.00 hp for HO and 75.00 kW | 100.00 hp for LO. HO supports 200% for 3S, 150% for 57S and 100% for 240S; LO supports 150% for 3S, 110% for 57S and 100% for 240S.
- Input and output data: Input and output each use 3 AC phases. Line voltage is 380 … 480 V ±10 %, line frequency is 47 … 63 Hz, and maximum output current is 220.00 A.
- Control frequency ranges: Output frequency is 0 … 200 Hz for vector control and 0 … 550 Hz for V/f control. Pulse frequency is 2 kHz.
- Integrated functions and protection: The module has an integrated Class A filter and braking chopper. Protection is IP20 / UL open type.
- Connections and cable lengths: Line-side and motor-end connections use M10 bolts with 35.00 … 120.00 mm2 conductors. The DC link uses screw-type terminals and 25.00 … 70.00 mm2 conductors; maximum motor cable length is 300 m shielded or 450 m unshielded.
- Mechanical data and conditions: Frame size is FSF. Dimensions are 708 mm high x 305 mm wide x 357 mm deep, with 63.00 kg net weight. Operation HO ambient temperature is -20 … 50 °C (-4 … 122 °F).
Frequently Asked Questions
1. What output ratings does the 6SL3210-1PE31-5AL0 power module provide?
It provides 55.00 kW | 75.00 hp rated output for HO and 75.00 kW | 100.00 hp for LO. Maximum output current is 220.00 A.
2. What input supply is required?
The input is 3 AC, 380 … 480 V ±10 % at 47 … 63 Hz.
3. Which control frequency ranges are available?
Output frequency is 0 … 200 Hz for vector control and 0 … 550 Hz for V/f control.
4. What connections and motor cable lengths are supported?
Line-side and motor-end connections use M10 bolts with 35.00 … 120.00 mm2 conductors. Maximum motor cable length is 300 m shielded or 450 m unshielded.
5. What is included or excluded from this configuration?
The module has an integrated Class A filter and braking chopper. It is without control unit and panel.