6SL3210-1PE11-8AL1

Siemens 6SL3210-1PE11-8AL1 SINAMICS Power Module PM240-2 with Class A filter, braking chopper, 3 AC input and 0.55 kW low-overload power. Request a model-specific quote.

Product Code
6SL3210-1PE11-8AL1
Dimensions
18.5 × 9 × 28 cm
Weight
1.55 kg
Lifecycle
Active Product
Availability
in stock
Lead Time
Confirmed with quotation
Product Attachment
Download Datasheet
Request Current Quote

Current status: in stock. Price, condition, lead time and warranty are confirmed in the quotation.

Product Overview

Technical Summary

Parameter Value
Input 3 AC, 380 … 480 V ±10 %, 47 … 63 Hz
Rated output power (LO) 0.55 kW | 0.75 hp
Rated output power (HO) 0.37 kW | 0.50 hp
Rated current (LO) 1.70 A
Rated current (HO) 1.30 A
Max. output current 2.60 A
Output frequency for vector control 0 … 200 Hz
Output frequency for V/f control 0 … 550 Hz
Connections Plug-in screw terminals
Frame size FSA
Degree of protection IP20 / UL open type

Key Features

  1. Power module and integrated functions: SINAMICS Power Module PM240-2 with an integrated Class A filter and braking chopper.
  2. Input and line supply: Input: 3 AC, 380 … 480 V ±10 %, 47 … 63 Hz; rated current: 2.30 A (LO) and 2.00 A (HO).
  3. Output power and current: Rated output power: 0.55 kW | 0.75 hp (LO) and 0.37 kW | 0.50 hp (HO); maximum output current: 2.60 A.
  4. Output frequency: Output frequency: 0 … 200 Hz for vector control and 0 … 550 Hz for V/f control.
  5. Connections and motor cable: Line-side and motor-end connections use plug-in screw terminals for 1.00 … 2.50 mm2 (AWG 18 … AWG 14) conductors. Maximum motor cable length is 50 m (164.04 ft) shielded or 100 m (328.08 ft) unshielded.
  6. Installation and protection: Frame size FSA, dimensions 73 mm × 196 mm × 165 mm (W × H × D), and degree of protection IP20 / UL open type. The module is without Control Unit and operating unit.

Frequently Asked Questions

1. What is the Siemens 6SL3210-1PE11-8AL1?

It is a SINAMICS Power Module PM240-2 with an integrated Class A filter and braking chopper.

2. What are the low-overload and high-overload output ratings?

Low overload is 0.55 kW | 0.75 hp with 1.70 A rated current; high overload is 0.37 kW | 0.50 hp with 1.30 A rated current.

3. What input supply does the module use?

Input is 3 AC, 380 … 480 V ±10 % at 47 … 63 Hz.

4. What connections and motor cable lengths are supported?

The line side and motor end use plug-in screw terminals for 1.00 … 2.50 mm2 (AWG 18 … AWG 14) conductors. Maximum motor cable length is 50 m (164.04 ft) shielded or 100 m (328.08 ft) unshielded.

5. What is included in the configuration?

It is without Control Unit and operating unit.

Send Inquiry