6ES7231-5QD50-0XB0

Siemens 6ES7231-5QD50-0XB0 SB 1231 TC provides 4 thermocouple inputs for J, K and other types, with ±80 mV range. Request a model-specific quote.

Product Code
6ES7231-5QD50-0XB0
Dimensions
8.2 × 3.4 × 7.9 cm
Weight
0.045 kg
Lifecycle
Active Product
Availability
in stock
Lead Time
Confirmed with quotation
Product Attachment
Download Datasheet
Request Current Quote

Current status: in stock. Price, condition, lead time and warranty are confirmed in the quotation.

Product Overview

Technical Summary

Parameter Value
Module type SB 1231, AI 4x 16-bit TC
Analog inputs 4; Thermocouples
Supported thermocouple types J, K, T, E, R, S, B, N, C, TXK/XK(L)
Rated voltage range -80 mV to +80 mV
Input resistance >= 10 MOhm
Resolution with overrange 15 bit; + sign
Integration time Parameterizable
Temperature compensation Parameterizable
Diagnostics Alarms, readable diagnostics, diagnostic alarm, wire break, DIAG LED
Protection IP20

Applications

  1. Thermocouple temperature measurement: Measures temperature signals from supported thermocouples using an integrating measurement principle; the temperature unit is adjustable to degrees Celsius or degrees Fahrenheit.

Key Features

  1. 4 analog thermocouple inputs: The SB 1231 TC has 4 analog inputs for thermocouples.
  2. Supported thermocouple types: Supports J, K, T, E, R, S, B, N, C and TXK/XK(L); TXK/TXK(L) to GOST is also supported.
  3. Rated input range: Rated voltage range: -80 mV to +80 mV. Input resistance in this range: >= 10 MOhm.
  4. Resolution and integration: Maximum resolution with overrange is 15 bit including sign. Integration time and temperature compensation are parameterizable.
  5. Diagnostics and indication: Provides alarms, readable diagnostics, diagnostic alarms, wire-break detection and a DIAG LED for input status.
  6. Connection and protection: Shielded cable length is maximum 100 m to the sensor. Isolation is tested with 707 V DC (type test), and protection is IP20.

Frequently Asked Questions

1. How many analog inputs does 6ES7231-5QD50-0XB0 have?

It has 4 analog thermocouple inputs.

2. Which thermocouple types are supported?

It supports J, K, T, E, R, S, B, N, C and TXK/XK(L), including TXK/TXK(L) to GOST.

3. What is the rated input voltage range?

The rated voltage range is -80 mV to +80 mV, with input resistance >= 10 MOhm in this range.

4. What diagnostic functions are available?

It provides alarms, readable diagnostics, diagnostic alarms, wire-break detection and a DIAG LED for input status.

Send Inquiry