6ES7144-6KD00-0AB0

Siemens 6ES7144-6KD00-0AB0 is a SIMATIC ET 200eco PN module with 8 analog inputs, PROFINET IO, 24 V supply and IP65/67 protection. Request a model-specific quote.

Product Code
6ES7144-6KD00-0AB0
Dimensions
20.3 × 7.3 × 5.8 cm
Weight
0.961 kg
Lifecycle
Product cancellation
Availability
in stock
Lead Time
Confirmed with quotation
Product Attachment
Download Datasheet
Request Current Quote

Current status: in stock. Price, condition, lead time and warranty are confirmed in the quotation.

Product Overview

Technical Summary

Parameter Value
Analog input channels 8 (4 voltage/current, 4 resistance/resistance thermometer)
Voltage input ranges 0 to +10 V; 1 V to 5 V; -10 V to +10 V; -80 mV to +80 mV
Current input ranges 0 to 20 mA; -20 mA to +20 mA; 4 mA to 20 mA
Maximum resolution 16 bit including sign
Integration time 2/16.67/20/100 ms, parameterizable
Conversion time per channel 4 / 19 / 22 / 102 ms
PROFINET interfaces 1
Network interface 100BASE-TX, up to 100 Mbit/s, M12 port, integrated switch
Rated supply 24 V DC
Connection and protection 8 M12 ports; IP65/67

Applications

  1. Analog signal measurement: Measures voltage, current, resistance, resistance thermometer and thermocouple signals through its analog inputs.
  2. PROFINET IO communication: Communicates analog input data using the supported PROFINET IO protocol.

Key Features

  1. Analog input channels: 8 analog inputs: 4 for voltage/current measurement and 4 for resistance/resistance thermometer measurement.
  2. Supported input ranges: Voltage ranges include 0 to +10 V, 1 V to 5 V, -10 V to +10 V and -80 mV to +80 mV; current ranges include 0 to 20 mA, -20 mA to +20 mA and 4 mA to 20 mA.
  3. Temperature and resistance inputs: Supports thermocouples Type E, Type J, Type K and Type N; resistance thermometer types include Ni 100, Ni 1000, Ni 120, Ni 200, Ni 500, Pt 100, Pt 1000, Pt 200 and Pt 500.
  4. PROFINET interface: 1 PROFINET interface with 100BASE-TX, integrated switch, M12 port and transmission rate up to 100 Mbit/s.
  5. Resolution and timing: Maximum resolution is 16 bit including sign; parameterizable integration time is 2/16.67/20/100 ms and conversion time per channel is 4 / 19 / 22 / 102 ms.
  6. Supply and protection: Rated supply is 24 V DC with reverse polarity protection; degree of protection is IP65/67 and connection uses 8 M12 ports.

Frequently Asked Questions

1. How many analog inputs does 6ES7144-6KD00-0AB0 have?

It has 8 analog inputs: 4 for voltage/current measurement and 4 for resistance/resistance thermometer measurement.

2. Which signal ranges are supported?

Supported voltage ranges are 0 to +10 V, 1 V to 5 V, -10 V to +10 V and -80 mV to +80 mV. Supported current ranges are 0 to 20 mA, -20 mA to +20 mA and 4 mA to 20 mA.

3. What PROFINET interfaces and protocols are available?

It has 1 PROFINET interface with 100BASE-TX, an M12 port and an integrated switch. PROFINET IO, SNMP, DCP, LLDP, ping and ARP are supported; TCP/IP, PROFINET CBA and PROFIsafe are not supported.

4. What are the resolution and conversion times?

Maximum resolution is 16 bit including sign. Parameterizable integration time is 2/16.67/20/100 ms, and conversion time per channel is 4 / 19 / 22 / 102 ms.

5. What supply and connection details should be verified?

Rated supply is 24 V DC, reverse polarity protection is provided, and the module has 8 M12 ports with IP65/67 protection.