Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Module type | F-DI 8x24VDC HF |
| Digital inputs | 8 |
| Input voltage, rated | 24 V DC |
| Signal 0 input voltage | -30 to +5 V |
| Signal 1 input voltage | +15 to +30 V |
| Counter counting frequency, max. | 500 Hz |
| Supply voltage, permissible | 19.2 V to 28.8 V DC |
| Diagnostics | Diagnostics function and diagnostic alarm; RUN, ERROR, PWR, channel-status and DIAG LEDs |
| Isolation | 707 V DC (type test) |
Applications
- Pulse counting: The module performs pulse counting through its parameterizable counter function.
- Standstill and speed monitoring: The module supports standstill and speed monitoring through its counter function.
Key Features
- Fail-safe digital inputs: F-DI 8x24VDC HF module with 8 parameterizable digital inputs and 24 V DC rated input voltage.
- Input signal ranges: Signal 0: -30 to +5 V; signal 1: +15 to +30 V. Typical signal-1 input current is 3.7 mA.
- Counter function: One parameterizable counter supports pulse counting, standstill and speed monitoring, with a maximum counting frequency of 500 Hz and up/down counting.
- Diagnostics and status LEDs: Diagnostics functions, diagnostic alarms, RUN, ERROR, PWR, channel-status and DIAG LEDs are supported.
- Supply and protection: Rated supply voltage is 24 V DC, with a permissible range of 19.2 V to 28.8 V and reverse-polarity protection.
- ET 200SP installation data: The module has 15 mm width, uses BU type A0 BaseUnits, and supports shielded cables up to 1 000 m or unshielded cables up to 500 m.
Frequently Asked Questions
1. How many digital inputs does 6ES7136-6BA01-0CA0 have?
It has 8 parameterizable digital inputs.
2. What input voltage signals does this module support?
The rated input voltage is 24 V DC. Signal 0 is -30 to +5 V, and signal 1 is +15 to +30 V.
3. Does the module support counter functions?
Yes. It supports 1 parameterizable counter with pulse counting, standstill and speed monitoring, up/down counting, and a maximum counting frequency of 500 Hz.
4. What diagnostics are available?
The module supports diagnostics functions and diagnostic alarms, with RUN, ERROR, PWR, channel-status and module DIAG LEDs.
5. Which BaseUnits and cable lengths should be checked before inquiry?
Usable BaseUnits are BU type A0. Maximum cable length is 1 000 m for shielded cable and 500 m for unshielded cable.