Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Module type | SIMATIC S7-300 isolated analog input module |
| Analog input channels | 8 |
| Supported voltage ranges | 1 V to 5 V; -1 V to +1 V; -10 V to +10 V; -5 V to +5 V; -500 mV to +500 mV; -80 mV to +80 mV |
| Supported current ranges | 0 to 20 mA; -20 mA to +20 mA; 4 mA to 20 mA |
| Resolution | 14 bit; Unipolar: 14 bit; bipolar: 13 bit + sign |
| Rated load voltage L+ | 24 V DC |
| Front connector | 20-pin |
| Diagnostics | Yes; diagnostic alarm and limit value alarm parameterizable |
| Isochronous mode | Yes |
| Product lifecycle | Product cancellation |
Applications
- Analog signal acquisition: The module supports analog voltage and current measurement, including connection of 2-wire and 4-wire transducers for current measurement.
Key Features
- 8 isolated analog inputs: The module has 8 analog inputs for voltage and current signals. The channels are not isolated from one another, but are isolated from the backplane bus and electronics power supply.
- Supported signal ranges: Voltage ranges include 1 V to 5 V, -1 V to +1 V, -10 V to +10 V, -5 V to +5 V, -500 mV to +500 mV, and -80 mV to +80 mV. Current ranges include 0 to 20 mA, -20 mA to +20 mA, and 4 mA to 20 mA.
- 14-bit resolution: Resolution with overrange is 14 bit; unipolar resolution is 14 bit and bipolar resolution is 13 bit + sign.
- Diagnostics and alarms: The module has diagnostics, readable diagnostic information, a parameterizable diagnostic alarm, and a parameterizable limit value alarm for channels 0 and 2. Group error SF indication is provided by a red LED.
- 24 V supply and 20-pin connection: Rated load voltage L+ is 24 V DC, with reverse polarity protection. The required front connector is 20-pin.
- Isochronous mode and dimensions: Isochronous mode is supported. The module measures 40 mm wide, 125 mm high, and 117 mm deep, with an approximate weight of 230 g.
Frequently Asked Questions
1. How many analog inputs does 6ES7331-7HF01-0AB0 have?
It has 8 analog inputs.
2. Which voltage and current ranges does the module support?
Supported voltage ranges are 1 V to 5 V, -1 V to +1 V, -10 V to +10 V, -5 V to +5 V, -500 mV to +500 mV, and -80 mV to +80 mV. Supported current ranges are 0 to 20 mA, -20 mA to +20 mA, and 4 mA to 20 mA.
3. What resolution does this analog input module provide?
Resolution with overrange is 14 bit; unipolar resolution is 14 bit and bipolar resolution is 13 bit + sign.
4. Does the module provide diagnostics and alarms?
Yes. It has readable diagnostic information, a parameterizable diagnostic alarm, a parameterizable limit value alarm for channels 0 and 2, and red LED indication for group error SF.
5. Which connector and supply does it require?
It requires a 20-pin front connector and has a rated load voltage L+ of 24 V DC.