Technical Summary
| Parameter | Value |
|---|---|
| Rated power (LO) | 15.00 kW | 20.00 hp |
| Rated power (HO) | 11.00 kW | 15.00 hp |
| Input voltage | 380 … 480 V +10 % -20 % |
| Input frequency | 47 … 63 Hz |
| Output frequency, vector control | 0 … 240 Hz |
| Output frequency, V/f control | 0 … 550 Hz |
| Maximum output current | 50.00 A |
| Digital inputs | 6 standard digital inputs + 1 fail-safe digital input |
| Analog I/O | 1 differential analog input; 1 non-isolated analog output |
| Communication | PROFIBUS DP |
| Protection | IP20 / UL open type |
| Frame size | FSC |
Key Features
- Rated power and overload: Rated power: 15.00 kW (LO) and 11.00 kW (HO). Low overload: 15,0 kW at 150% for 3s, 110% for 57s, and 100% for 240s; high overload: 11,0 kW at 200% for 3s, 150% for 57s, and 100% for 240s.
- Input and output data: Input: 3 AC, 380 … 480 V +10 % -20 %, 47 … 63 Hz. Output: 3 AC, 400V IEC | 480V NEC, maximum output current 50.00 A, and output frequency up to 0 … 240 Hz with vector control or 0 … 550 Hz with V/f control.
- I/O and safety: The interface has 6 standard digital inputs, 1 fail-safe digital input, 1 relay changeover contact, 1 transistor output, 1 differential analog input, and 1 non-isolated analog output. Safe Torque Off is integrated.
- Communication and installation: Communication: PROFIBUS DP. Protection: IP20 / UL open type. Line-side, motor-end, and DC-link connections use plug-in screw terminals; frame size is FSC, with dimensions of 140 mm width and 203 mm depth.
Frequently Asked Questions
1. What is the rated power of Siemens 6SL3210-1KE23-2AP1?
Rated power is 15.00 kW (LO) or 11.00 kW (HO).
2. What I/O does this SINAMICS G120C drive provide?
It has 6 standard digital inputs, 1 fail-safe digital input, 1 relay changeover contact, 1 transistor output, 1 differential analog input, and 1 non-isolated analog output.
3. Which communication interface is included?
Communication is PROFIBUS DP.
4. How is the drive connected and protected?
Line-side, motor-end, and DC-link connections use plug-in screw terminals. Protection is IP20 / UL open type, and the frame size is FSC.