Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Module type | AI 2xU/I 2-4-wire HF |
| Analog inputs | 2 differential inputs |
| Voltage input ranges | 0 to +10 V; 1 V to 5 V; -10 V to +10 V; -5 V to +5 V |
| Current input ranges | 0 to 20 mA; -20 mA to +20 mA; 4 mA to 20 mA |
| Resolution | Up to 16 bit including sign |
| Supply voltage | 24 V DC; permissible range 19.2 V to 28.8 V |
| Connection variants | 2-wire and 4-wire; BU type A0, A1 |
| Diagnostics | Channel, supply-voltage, wire-break, short-circuit, group error, overflow/underflow |
| Conversion time | 0.9 ms to 68.2 ms per channel |
| Operating temperature | -40 °C to 60 °C horizontal installation; +70 °C for 10 minutes |
Key Features
- Analog inputs: 2 differential analog inputs support voltage and current measurement.
- Input ranges: Voltage ranges include 0 to +10 V, 1 V to 5 V, -10 V to +10 V, and -5 V to +5 V; current ranges include 0 to 20 mA, -20 mA to +20 mA, and 4 mA to 20 mA.
- Resolution: Resolution with overrange is up to 16 bit including sign.
- Diagnostics: The module has channel diagnostics, supply-voltage monitoring, wire-break detection for 4 to 20 mA, channel-by-channel short-circuit detection, group error, and overflow/underflow diagnostics.
- Supply and protection: Rated supply is 24 V DC, with a permissible range of 19.2 V to 28.8 V and reverse polarity protection.
- Installation and dimensions: The module supports BU type A0, A1 for 2-wire and 4-wire connections and measures 15 mm wide, 73 mm high, and 58 mm deep.
Frequently Asked Questions
1. How many analog inputs does the 6AG2134-6HB00-1CA1 have?
It has 2 differential analog inputs for voltage and current measurement.
2. Which signal ranges does the module support?
Voltage ranges are 0 to +10 V, 1 V to 5 V, -10 V to +10 V, and -5 V to +5 V. Current ranges are 0 to 20 mA, -20 mA to +20 mA, and 4 mA to 20 mA.
3. What diagnostics are available?
It has channel diagnostics, supply-voltage monitoring, wire-break detection for 4 to 20 mA, channel-by-channel short-circuit detection, group error, and overflow/underflow diagnostics.
4. Which BaseUnits and connection variants are supported?
BU type A0 and A1 support both 2-wire and 4-wire connections.