6SL3210-1PE31-5UL0

Siemens 6SL3210-1PE31-5UL0 SINAMICS G120 PM240-2 power module with 55 kW high-overload output, IP20 protection and built-in braking chopper. Request a model-specific quote.

Product Code
6SL3210-1PE31-5UL0
Dimensions
74.5 × 46.9 × 38.5 cm
Weight
58 kg
Lifecycle
Active Product
Availability
in stock
Lead Time
Confirmed with quotation
Product Attachment
Download Datasheet
Request Current Quote

Current status: in stock. Price, condition, lead time and warranty are confirmed in the quotation.

Product Overview

Technical Summary

Parameter Value
High-overload rated power 55.00 kW | 75.00 hp (HO)
Low-overload rated power 75.00 kW | 100.00 hp (LO)
High-overload rated current 110.00 A (HO)
Low-overload rated current 145.00 A (LO)
Input supply 3 AC, 380 … 480 V ±10 %, 47 … 63 Hz
Maximum output current 220.00 A
Vector-control output frequency 0 … 200 Hz
V/f-control output frequency 0 … 550 Hz
Frame size FSF
Degree of protection IP20 / UL open type
Braking resistor connection Screw-type terminals; cable length 10 m (32.81 ft)

Key Features

  1. High-overload output: Rated power: 55.00 kW | 75.00 hp (HO); rated current: 110.00 A (HO).
  2. Low-overload output: Rated power: 75.00 kW | 100.00 hp (LO); rated current: 145.00 A (LO).
  3. Input supply: Input: 3 AC, 380 … 480 V ±10 %, 47 … 63 Hz.
  4. Output control ranges: Output frequency: 0 … 200 Hz for vector control and 0 … 550 Hz for V/f control.
  5. Connections and braking: Line-side and motor-end connections use M10 bolts; the DC link for a braking resistor uses screw-type terminals and has a 10 m (32.81 ft) cable length.
  6. Installation and protection: Frame size: FSF. Dimensions: 708 mm × 305 mm × 357 mm (H×W×D). Degree of protection: IP20 / UL open type. The module is without a control unit and panel.

Frequently Asked Questions

1. What is the high-overload output rating of 6SL3210-1PE31-5UL0?

The high-overload rated power is 55.00 kW | 75.00 hp (HO), with a rated current of 110.00 A (HO).

2. What input supply does this power module use?

The input is 3 AC, 380 … 480 V ±10 % at 47 … 63 Hz.

3. What output frequency ranges are supported?

The output frequency is 0 … 200 Hz for vector control and 0 … 550 Hz for V/f control.

4. How is the braking resistor connected?

The DC link for a braking resistor uses screw-type terminals, with a cable length of 10 m (32.81 ft).

5. What is included in the configuration?

It is without a control unit and panel, and without a filter.

Send Inquiry