6AG1221-1BF32-4XB0

Siemens 6AG1221-1BF32-4XB0 SIPLUS SM 1221 digital input module with 8 DI, 24 V DC input, diagnostics, and IP20 protection. Request a model-specific quote.

Product Code
6AG1221-1BF32-4XB0
Dimensions
10.5 × 9 × 5.7 cm
Weight
0.16 kg
Lifecycle
Active Product
Availability
in stock
Lead Time
Confirmed with quotation
Product Attachment
Download Datasheet
Request Current Quote

Current status: in stock. Price, condition, lead time and warranty are confirmed in the quotation.

Product Overview

Technical Summary

Parameter Value
Product type SM 1221, DI 8×24 V DC
Digital input channels 8, in groups of 2
Rated input voltage 24 V DC
Permissible supply voltage 20.4 V to 28.8 V DC
Signal 0 5 V DC at 1 mA
Signal 1 15 V DC at 2.5 mA
Input delay options 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four
Protection IP20
Operating ambient temperature -20 °C to 60 °C; start-up at 0 °C
Front connector Required

Applications

  1. Digital signal acquisition: The module acquires 24 V DC digital signals through 8 digital inputs.
  2. Interrupt input diagnostics: The module supports parameterizable interrupt inputs with diagnostics, diagnostic alarms, and input-status LED indication.

Key Features

  1. Digital inputs: 8 digital inputs for 24 V DC signals, arranged in groups of 2.
  2. Input signal thresholds: Signal 0: 5 V DC at 1 mA; signal 1: 15 V DC at 2.5 mA.
  3. Supply voltage: Rated supply and input voltage: 24 V DC; permissible supply range: 20.4 V to 28.8 V.
  4. Diagnostics: Diagnostics function, diagnostic alarm, and input-status LED indication are provided.
  5. Conformal coating: Conformal coating is provided for high-reliability printed circuit board assemblies; Type 1 protection against fouling.
  6. Installation and protection: The module requires a front connector, has IP20 protection, and measures 45 mm wide, 100 mm high, and 75 mm deep.

Frequently Asked Questions

1. How many digital inputs does 6AG1221-1BF32-4XB0 have?

It has 8 digital inputs, arranged in groups of 2.

2. What input voltage does the module use?

The rated input voltage is 24 V DC. Signal 0 is 5 V DC at 1 mA, and signal 1 is 15 V DC at 2.5 mA.

3. Does the module provide diagnostics?

Yes. It has a diagnostics function, diagnostic alarm, and LED indication for input status.

4. What connector is required?

A front connector is required.

Send Inquiry