Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Module type | SIPLUS S7-1500 digital input module |
| Digital inputs | 16; groups of 1 |
| Rated input voltage, DC | 24 V; 48 V; 125 V |
| Rated input voltage, AC | 24 V; 48 V; 125 V (50 – 60 Hz) |
| Signal 0 | -5 … +5 V |
| Signal 1 | +11 … +146 V |
| Input delay | 0.05 / 0.1 / 0.4 / 1.6 / 3.2 / 12.8 / 20 ms DC; 20 ms fixed AC |
| Counting frequency, max. | 6 kHz |
| Power consumption from backplane bus | 1.2 W |
| Power loss, typ. | 2.2 W at 24 V DC; 6.0 W at 125 V AC |
Key Features
- Digital input channels: 16 digital inputs in groups of 1; above +60 °C, a maximum of 4 non-adjacent inputs can be controlled simultaneously.
- Input voltage: Rated input values are 24 V, 48 V and 125 V DC, or 24 V, 48 V and 125 V AC at 50 – 60 Hz.
- Signal ranges: Signal 0: -5 … +5 V. Signal 1: +11 … +146 V; typical current is 3 mA at 24 V DC.
- Input delay: Parameterizable DC input delay: 0.05 / 0.1 / 0.4 / 1.6 / 3.2 / 12.8 / 20 ms; AC input delay is fixed at 20 ms.
- Diagnostics and interrupts: The module has diagnostics, diagnostic alarms, hardware interrupts, wire-break detection to I < 550 μA, and green or red diagnostic LEDs.
- Electrical isolation: Channels are electrically isolated from one another in groups of 1 and isolated from the backplane bus; permissible difference between different circuits is 146 V DC/132 V AC.
Frequently Asked Questions
1. How many digital inputs does Siemens 6AG1521-7EH00-7AB0 have?
It has 16 digital inputs in groups of 1. Above +60 °C, a maximum of 4 non-adjacent inputs can be controlled simultaneously.
2. Which input voltage ranges does this module support?
Rated input values are 24 V, 48 V and 125 V DC, or 24 V, 48 V and 125 V AC at 50 – 60 Hz. Signal 0 is -5 … +5 V and signal 1 is +11 … +146 V.
3. What input delay settings are available?
For DC, the parameterizable settings are 0.05 / 0.1 / 0.4 / 1.6 / 3.2 / 12.8 / 20 ms. For AC, the input delay is fixed at 20 ms.
4. What diagnostics does the module provide?
It provides diagnostics, diagnostic alarms, hardware interrupts, wire-break detection to I < 550 μA, and green or red diagnostic LEDs.