Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Product type | SIPLUS S7-400 interface module DP master |
| Based on | 6ES7964-2AA04-0AB0 |
| PROFIBUS DP master transmission rate, max. | 12 Mbit/s |
| Maximum number of DP devices | 125; depending on the CPU used |
| Current consumption, max. | 150 mA at the DP interface components |
| Power loss, typ. | 1 W |
| Operating ambient temperature | -25 °C to 70 °C; 70 °C at 60°C for UL/ATEX/FM use |
| Installation altitude above sea level, max. | 5 000 m |
Applications
- PROFIBUS DP master communication: Provides PROFIBUS DP master communication with connected DP devices, including direct data exchange, SYNC/FREEZE, and equidistance.
- PG/OP communication: Supports PG/OP communication through the PROFIBUS DP interface.
Key Features
- PROFIBUS DP master interface: Supports PROFIBUS DP master and PROFIBUS DP device operation, with PG/OP communication, equidistance, SYNC/FREEZE, and direct data exchange.
- Transmission rate and device count: Maximum PROFIBUS DP master transmission rate is 12 Mbit/s; maximum number of DP devices is 125, depending on the CPU used.
- Cable length: Maximum cable length is 1 200 m at 9.6 kbit/s and 100 m at 12 Mbit/s.
- Current and power loss: Total current consumption of components connected to the DP interface is maximum 150 mA; isolated 5 V (P5ext) current carrying capacity is maximum 90 mA, 24 V current carrying capacity is maximum 150 mA, and typical power loss is 1 W.
- Environmental protection: The module has conformal coating, with an operating ambient temperature from -25 °C to 70 °C. The 70 °C maximum applies at 60°C for UL/ATEX/FM use.
- Dimensions and weight: Dimensions are 26 mm width, 54 mm height, and 130 mm depth; approximate weight is 65 g.
Frequently Asked Questions
1. What communication function does 6AG1964-2AA04-7AB0 provide?
It supports PROFIBUS DP master and PROFIBUS DP device operation, including PG/OP communication, equidistance, SYNC/FREEZE, and direct data exchange.
2. What PROFIBUS DP transmission rate and cable length are supported?
The maximum transmission rate is 12 Mbit/s. Maximum cable length is 1 200 m at 9.6 kbit/s and 100 m at 12 Mbit/s.
3. How many DP devices can the module support?
The maximum number is 125 DP devices, depending on the CPU used.
4. What are the operating temperature and dimensions?
The operating ambient temperature is -25 °C to 70 °C, with 70 °C at 60°C for UL/ATEX/FM use. Dimensions are 26 mm width, 54 mm height, and 130 mm depth.