6ES7141-5BF00-0BL0

Siemens 6ES7141-5BF00-0BL0 SIMATIC ET 200AL IO-Link digital input module with 8 DI, 24 V DC signals, M8 inputs and IP67 protection. Request a model-specific quote.

Product Code
6ES7141-5BF00-0BL0
Dimensions
17.9 × 4.7 × 4.2 cm
Weight
0.143 kg
Lifecycle
Active Product
Availability
in stock
Lead Time
Confirmed with quotation
Product Attachment
Download Datasheet
Request Current Quote

Current status: in stock. Price, condition, lead time and warranty are confirmed in the quotation.

Product Overview

Technical Summary

Parameter Value
Digital inputs 8
Input voltage, rated value 24 V DC
Input voltage for signal 0 -30 to +5 V
Input voltage for signal 1 +11 to +30V
IO-Link protocol 1.1
Input connection M8, 3-pole
IO-Link connection M12, 5-pin, A-coded
Protection IP65/67
Ambient temperature during operation -30 °C to 55 °C
Product lifecycle Active Product

Applications

  1. Digital signal acquisition: Acquires digital signals through 8 digital inputs for 24 V DC signals.

Key Features

  1. IO-Link digital input module: Product type designation: IO-Link DI 8x24VDC with 8 digital inputs and IO-Link protocol 1.1.
  2. 24 V DC input signals: Rated input voltage: 24 V DC; signal 0: -30 to +5 V; signal 1: +11 to +30V.
  3. M8 input connections: Electrical connection for inputs and outputs: M8, 3-pole; IO-Link connection: M12, 5-pin, A-coded.
  4. Diagnostics: Parameterizable diagnostic alarm, short-circuit diagnosis, green channel-status LED, and green/red module-diagnostics LED.
  5. Supply and protection: Load voltage rated value: 24 V DC, supplied from 1Us+ of the IO-Link master; IP degree of protection: IP65/67.
  6. Installation data: Dimensions: 30 mm width, 159 mm height, and 40 mm depth. All mounting positions support up to 8 at 55 °C max.

Frequently Asked Questions

1. How many digital inputs does the Siemens 6ES7141-5BF00-0BL0 have?

It has 8 digital inputs.

2. What input voltage ranges does this module support?

The rated input voltage is 24 V DC. Signal 0 is -30 to +5 V, and signal 1 is +11 to +30V.

3. Which connections are provided?

The inputs and outputs use M8, 3-pole connections. The IO-Link connection uses M12, 5-pin, A-coded.

4. What diagnostics does the module provide?

It has a parameterizable diagnostic alarm, short-circuit diagnosis, a green channel-status LED, and a green/red module-diagnostics LED.

Send Inquiry