| Parameter | Value |
|---|---|
| Product type | SINAMICS G120 PM 240 Power Module |
| Supply | 380-480 V 3 AC +10/-10%, 47-63 Hz |
| High overload power | 132 kW at 160% 3 s, 136% 57 s, 100% 240 s; ambient temperature 0 to +50 °C |
| Low overload power | 160 kW at 150% 3 s, 110% 57 s, 100% 240 s; ambient temperature 0 to +40 °C |
| Configuration | Unfiltered, without integrated braking chopper, Control Unit, or BOP |
| Degree of protection | IP20 |
Key Features
- Power module: SINAMICS G120 PM 240 Power Module; spare part and product cancellation.
- Supply: 380-480 V 3 AC +10/-10%, 47-63 Hz.
- High overload power: 132 kW at 160% for 3 s, 136% for 57 s, and 100% for 240 s; ambient temperature 0 to +50 °C.
- Low overload power: 160 kW at 150% for 3 s, 110% for 57 s, and 100% for 240 s; ambient temperature 0 to +40 °C.
- Configuration: Unfiltered, without an integrated braking chopper, Control Unit, or BOP.
- Protection and weight: Degree of protection IP20; net weight 170.000 kg; packaging dimensions 83.00 x 61.00 x 177.00 cm.
Frequently Asked Questions
1. What supply does the 6SL3224-0XE41-3UA0 use?
It uses 380-480 V 3 AC +10/-10% at 47-63 Hz.
2. What are the high- and low-overload power ratings?
High overload is 132 kW at 160% for 3 s, 136% for 57 s, and 100% for 240 s at 0 to +50 °C ambient temperature. Low overload is 160 kW at 150% for 3 s, 110% for 57 s, and 100% for 240 s at 0 to +40 °C ambient temperature.
3. What is included in this configuration?
It is unfiltered and without an integrated braking chopper, Control Unit, or BOP.