Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Module type | SINAMICS G120 PM 240-2 power module |
| Mounting form | Push-through |
| Supply | 380-480 V 3 AC +10/-20% |
| Frequency | 47-63 Hz |
| High overload power | 45 kW |
| High overload profile | 200% 3 s, 150% 57 s, 100% 240 s |
| High overload ambient temperature | -20 to +50 °C (HO) |
| Low overload power | 55 kW |
| Low overload profile | 150% 3 s, 110% 57 s, 100% 240 s |
| Integrated functions | Class A filter and braking chopper |
| Protection | FSE, IP20 |
Key Features
- Power module: SINAMICS G120 PM 240-2 power module with push-through mounting.
- Supply and frequency: Supply: 380-480 V 3 AC +10/-20%; frequency: 47-63 Hz.
- High overload rating: 45 kW at 200% for 3 s, 150% for 57 s, and 100% for 240 s; ambient temperature: -20 to +50 °C (HO).
- Low overload rating: 55 kW at 150% for 3 s, 110% for 57 s, and 100% for 240 s; ambient temperature: -20 to +40 °C (LO).
- Integrated functions and protection: Integrated Class A filter and braking chopper; FSE degree of protection: IP20. Without Control Unit and operating unit.
- Lifecycle and firmware: Product cancellation; released as of CU firmware version V4.7 SP6.
Frequently Asked Questions
1. What type of module is Siemens 6SL3211-1PE31-1AL0?
It is a SINAMICS G120 PM 240-2 power module with push-through mounting.
2. What supply does this power module use?
Supply is 380-480 V 3 AC +10/-20% at 47-63 Hz.
3. What are the high and low overload ratings?
High overload is 45 kW at 200% for 3 s, 150% for 57 s, and 100% for 240 s. Low overload is 55 kW at 150% for 3 s, 110% for 57 s, and 100% for 240 s.
4. Which integrated functions and protection are provided?
It has an integrated Class A filter, an integrated braking chopper, and FSE degree of protection IP20.
5. What is excluded from this configuration?
It is without Control Unit and operating unit.