Product Overview

Technical Summary

Parameter Value
Module type SINAMICS G120 PM 240-2 push-through power module
Supply 380-480 V 3 AC +10/-20%, 47-63 Hz
Integrated functions Class A filter and braking chopper
High-overload power 30 kW
High-overload profile 200% 3 s, 150% 57 s, 100% 240 s; -20 to +50 °C (HO)
Low-overload power 37 kW
Low-overload profile 150% 3 s, 110% 57 s, 100% 240 s; -20 to +40 °C (LO)
Protection IP20
Excluded components Control Unit and operation panel
Firmware release CU firmware version V4.7 SP6
Lifecycle Product cancellation

Key Features

  1. Power module type: SINAMICS G120 PM 240-2 push-through power module with integrated Class A filter and braking chopper.
  2. Supply: 380-480 V 3 AC +10/-20%, 47-63 Hz.
  3. High-overload rating: 30 kW at 200% for 3 s, 150% for 57 s, and 100% for 240 s; ambient temperature -20 to +50 °C (HO).
  4. Low-overload rating: 37 kW at 150% for 3 s, 110% for 57 s, and 100% for 240 s; ambient temperature -20 to +40 °C (LO).
  5. Dimensions and protection: 517x275x237 mm (HxWxD), IP20; without Control Unit and operation panel.
  6. Lifecycle and firmware: Product cancellation; released as of CU firmware version V4.7 SP6.

Frequently Asked Questions

1. What is the exact function of the 6SL3211-1PE27-5AL0?

It is a SINAMICS G120 PM 240-2 push-through power module with an integrated Class A filter and braking chopper.

2. What supply does this power module use?

Supply is 380-480 V 3 AC +10/-20% at 47-63 Hz.

3. What are the high-overload and low-overload ratings?

High overload is 30 kW at 200% for 3 s, 150% for 57 s, and 100% for 240 s. Low overload is 37 kW at 150% for 3 s, 110% for 57 s, and 100% for 240 s.

4. Is the Control Unit included?

It is without the Control Unit and operation panel.