6SL3211-1PE18-0UL1

Siemens 6SL3211-1PE18-0UL1 SINAMICS PM240-2 power module with integrated braking chopper, IP20-PT protection and 380-480 V 3AC supply. Request a model-specific quote.

Product Code
6SL3211-1PE18-0UL1
Dimensions
20 × 17.5 × 17.5 cm
Weight
1.8 kg
Lifecycle
Product cancellation
Availability
in stock
Lead Time
Confirmed with quotation

Product Tags

Request Current Quote

Current status: in stock. Price, condition, lead time and warranty are confirmed in the quotation.

Product Overview

Technical Summary

Parameter Value
Power module SINAMICS Power Module PM240-2, unfiltered, with integrated braking chopper
Supply 380-480 V 3AC +10/-10%, 47-63 Hz
High overload power 2.2 kW
High overload profile 200% for 3 s, 150% for 57 s, 100% for 240 s; ambient temperature -10 to +50 °C
Low overload power 3 kW
Low overload profile 150% for 3 s, 110% for 57 s, 100% for 240 s; ambient temperature -10 to +40 °C
Form factor FSA
Degree of protection IP20-PT
Excluded components Without Control Unit and operating unit
Firmware release Released as of CU Firmware version V4.6
Lifecycle Product cancellation

Key Features

  1. Power module type: SINAMICS Power Module PM240-2, unfiltered, with an integrated braking chopper.
  2. Supply: 380-480 V 3AC +10/-10%, 47-63 Hz.
  3. High overload rating: 2.2 kW at 200% for 3 s, 150% for 57 s and 100% for 240 s; ambient temperature -10 to +50 °C.
  4. Low overload rating: 3 kW at 150% for 3 s, 110% for 57 s and 100% for 240 s; ambient temperature -10 to +40 °C.
  5. Installation and protection: 238 x 126 x 171 mm (H x W x D), FSA, degree of protection IP20-PT.
  6. Configuration and lifecycle: Without Control Unit and operating unit; released as of CU Firmware version V4.6. Product cancellation.

Frequently Asked Questions

1. What type of module is 6SL3211-1PE18-0UL1?

It is a Siemens SINAMICS Power Module PM240-2, unfiltered, with an integrated braking chopper.

2. What supply does this power module use?

The supply is 380-480 V 3AC +10/-10% at 47-63 Hz.

3. What are the high and low overload ratings?

High overload is 2.2 kW at 200% for 3 s, 150% for 57 s and 100% for 240 s, with ambient temperature -10 to +50 °C. Low overload is 3 kW at 150% for 3 s, 110% for 57 s and 100% for 240 s, with ambient temperature -10 to +40 °C.

4. What is included in the configuration?

It is without Control Unit and operating unit.

5. What are the dimensions and protection degree?

The dimensions are 238 x 126 x 171 mm (H x W x D), with FSA form factor and IP20-PT degree of protection.

Send Inquiry