6SL3211-1PC22-8AL0

Siemens 6SL3211-1PC22-8AL0 SINAMICS PM240-2 power module with integrated Class A filter and braking chopper. 200-240 V 3AC supply. Request a model-specific quote.

Product Code
6SL3211-1PC22-8AL0
Dimensions
24.5 × 20.5 × 44.2 cm
Weight
6.3 kg
Lifecycle
Product cancellation
Availability
in stock
Lead Time
Confirmed with quotation

Product Tags

Request Current Quote

Current status: in stock. Price, condition, lead time and warranty are confirmed in the quotation.

Product Overview

Technical Summary

Parameter Value
Module type SINAMICS Power Module PM240-2
Supply 200-240 V 3AC +10/-10%, 47-63 Hz
High overload power 5.5 kW
High overload duration 200% 3 s, 150% 57 s, 100% 240 s
High overload ambient temperature -10 to +50 °C
Low overload power 7.5 kW
Low overload duration 150% 3 s, 110% 57 s, 100% 240 s
Low overload ambient temperature -10 to +40 °C
Protection IP20-PT
Included functions Integrated Class A filter and integrated braking chopper
Excluded components Control Unit and operation panel
Firmware release CU firmware version V4.6

Key Features

  1. Power module type: SINAMICS Power Module PM240-2 with integrated Class A filter and integrated braking chopper.
  2. Supply: 200-240 V 3AC +10/-10%, 47-63 Hz.
  3. High overload rating: 5.5 kW at 200% for 3 s, 150% for 57 s, and 100% for 240 s; ambient temperature -10 to +50 °C.
  4. Low overload rating: 7.5 kW at 150% for 3 s, 110% for 57 s, and 100% for 240 s; ambient temperature -10 to +40 °C.
  5. Protection: IP20-PT.
  6. Configuration and lifecycle: Without Control Unit and operation panel; product cancellation. Released as of CU firmware version V4.6.

Frequently Asked Questions

1. What is the 6SL3211-1PC22-8AL0 configuration?

It is a SINAMICS Power Module PM240-2 with an integrated Class A filter and integrated braking chopper. It is without Control Unit and operation panel.

2. What supply does this power module use?

Supply: 200-240 V 3AC +10/-10%, 47-63 Hz.

3. What are the overload ratings?

High overload: 5.5 kW at 200% for 3 s, 150% for 57 s, and 100% for 240 s at -10 to +50 °C. Low overload: 7.5 kW at 150% for 3 s, 110% for 57 s, and 100% for 240 s at -10 to +40 °C.

4. What protection rating does it have?

Protection: IP20-PT.

5. What should be verified before requesting a quote?

Verify the exact order number, the required overload rating and ambient temperature range, and that the Control Unit and operation panel are supplied separately.

Send Inquiry