Product Overview

Technical Summary

Parameter Value
Product type Soft starter
Rated operational current at 40 °C, standard circuit 93 A
Rated motor power at 400 V, standard circuit 45 kW
Rated operational current at 40 °C, inside-delta circuit 161 A
Rated motor power at 400 V, inside-delta circuit 90 kW
Operating voltage 200 … 460 V AC
Control supply 230 V AC at 50 Hz and 60 Hz
Main current connection Box terminal
Auxiliary and control connection Spring-loaded terminals
Mounting Screw fixing; vertical mounting surface +/-90° rotatable and +/- 22.5° tiltable to the front and back
Front protection IP20 according to IEC 60529
Product lifecycle Start of final year of support

Applications

  1. Motor starting: Controls motor starting through a soft-start function using thyristors and an integrated bypass contact system.
  2. Motor protection: Provides intrinsic device protection, motor overload protection, and evaluation of thermistor motor protection.
  3. Motor braking: Provides a motor brake output.

Key Features

  1. Soft-start motor control: Soft starter with thyristors, integrated bypass contact system, intrinsic device protection, motor overload protection, and adjustable current limitation.
  2. Standard-circuit rating: Rated operational current is 93 A at 40 °C; rated motor power is 45 kW at 400 V in standard circuit.
  3. Inside-delta operation: Inside-delta circuit supports 161 A at 40 °C and 90 kW at 400 V; minimum load is 8 %.
  4. Voltage and control supply: Operating voltage is 200 … 460 V in standard and inside-delta circuits. The AC control supply is 230 V at 50 Hz and 60 Hz.
  5. Protection and functions: The device has evaluation of thermistor motor protection, external reset, a motor brake output, and a Display version for fault signals.
  6. Installation and connections: Dimensions are 170 mm wide, 192 mm high, and 270 mm deep. Screw fixing, box terminal for the main current circuit, and spring-loaded terminals for auxiliary and control circuits.

Frequently Asked Questions

1. What is the rated current of the Siemens 3RW4427-3BC44?

The rated operational current is 93 A at 40 °C in standard circuit, or 161 A at 40 °C in inside-delta circuit.

2. What motor power is supported at 400 V?

The rated motor power is 45 kW at 400 V in standard circuit and 90 kW at 400 V in inside-delta circuit.

3. What operating and control voltages does it use?

Operating voltage is 200 … 460 V in both standard and inside-delta circuits. The AC control supply is 230 V at 50 Hz and 60 Hz.

4. How is the soft starter connected and mounted?

It uses a box terminal for the main current circuit and spring-loaded terminals for auxiliary and control circuits. Mounting is by screw fixing.