6ES7138-4CF42-0AB0

SIMATIC DP PM-E F PROFIsafe power module for ET200S with 24 V DC load voltage, relay output and diagnostics. Request a model-specific quote.

Product Code
6ES7138-4CF42-0AB0
Dimensions
9.1 × 6.5 × 4 cm
Weight
0.096 kg
Lifecycle
Product cancellation
Availability
in stock
Lead Time
Confirmed with quotation
Product Attachment
Download Datasheet

Product Tags

Request Current Quote

Current status: in stock. Price, condition, lead time and warranty are confirmed in the quotation.

Product Overview

Technical Summary

Parameter Value
Module type SIMATIC DP PM-E F PROFIsafe power module for ET200S
Load voltage L+ 24 V DC rated value
Digital output 1 relay output; controls a digital input
Output short-circuit protection No
Typical input current 100 mA from load voltage L+ without load
Typical power loss 4 W
Diagnostics Short-circuit and missing load voltage detected; wire break: No
Safety ratings Category 3 (EN 954-1), PL e (ISO 13849-1), SIL 2 with Std-DO or SIL 3 without Std-DO depending on configuration

Applications

  1. Voltage-bus switching: Switching the P1 and P2 voltage buses with a grounded setup relay.
  2. Digital-input control: Controlling a digital input through the relay digital output.

Key Features

  1. Power module function: Suitable for grounded setup relay switching of the P1 and P2 voltage buses up to Category 3 (EN 954-1), SIL2 (IEC61508), and PLD (ISO13849).
  2. Supply and power loss: Rated load voltage L+: 24 V DC; typical input current from load voltage L+ without load: 100 mA; typical power loss: 4 W.
  3. Relay digital output: 1 relay digital output; it can control a digital input. Short-circuit protection: No.
  4. Switching capacity: Maximum switching capacity on lamp load: 100 W. Maximum switching frequency: 2 Hz with resistive or lamp load, and 0.1 Hz with inductive load to IEC 60947-5-1, DC-13 / AC-15.
  5. Diagnostics and isolation: Diagnostics function and readable diagnostic information are available. The module detects short-circuit and missing load voltage; group error SF is indicated by a red LED.
  6. Installation and dimensions: Maximum current for horizontal installation is 10 A up to 40 °C, 8 A up to 55 °C, and 7 A up to 60 °C; vertical installation is 8 A up to 40 °C. Dimensions: 30 mm x 81 mm x 52 mm.

Frequently Asked Questions

1. What voltage does the Siemens 6ES7138-4CF42-0AB0 use?

Its rated load voltage L+ is 24 V DC.

2. How many digital outputs does the module have?

It has 1 relay digital output, which can control a digital input.

3. What diagnostics are available?

The module provides a diagnostics function and readable diagnostic information, and detects short-circuit and missing load voltage. Wire-break detection is not available.

4. What are the switching limits of the output?

The maximum switching capacity on lamp load is 100 W. Switching frequency is maximum 2 Hz with resistive or lamp load and 0.1 Hz with inductive load to IEC 60947-5-1, DC-13 / AC-15.

5. What should be verified before requesting a quote?

Verify the required installation orientation and temperature condition: horizontal installation permits 10 A up to 40 °C, 8 A up to 55 °C, or 7 A up to 60 °C; vertical installation permits 8 A up to 40 °C.

Send Inquiry