Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Digital output channels | 16 isolated DO |
| Rated load voltage | 24 V DC |
| Permissible load-voltage range | 20.4 V to 28.8 V |
| Rated output current | 0.5 A |
| Output current range, 0 to 40 °C | 5 mA to 0.6 A |
| Output current range, 40 to 60 °C | 5 mA to 0.6 A |
| Resistive-load switching frequency, max. | 100 Hz |
| Inductive-load switching frequency, max. | 0.5 Hz |
| Lamp-load switching frequency, max. | 10 Hz |
| Power loss, typ. | 4.9 W |
| Isolation | 500 V DC test voltage |
Applications
- Digital input control: The outputs can control a digital input.
- Redundant load control: The module supports redundant control of a load.
Key Features
- Digital outputs: 16 isolated digital outputs with 0.5 A rated output current.
- Load voltage: Rated load voltage: 24 V DC; permissible range: 20.4 V to 28.8 V.
- Output protection: Electronic short-circuit protection is provided.
- Output isolation: Digital outputs are isolated between channels in groups of 8 and from the backplane bus by optocoupler.
- Switching frequency: Maximum switching frequency is 100 Hz with resistive load, 0.5 Hz with inductive load, and 10 Hz with lamp load.
- Conformal coating and temperature: SIPLUS version with conformal coating and a -25…+70 °C temperature range.
Frequently Asked Questions
1. How many digital outputs does 6AG1322-1BH01-2AA0 have?
It has 16 isolated digital outputs.
2. What load voltage does this module use?
The rated load voltage is 24 V DC, with a permissible range of 20.4 V to 28.8 V.
3. What is the rated output current?
The rated output current is 0.5 A. For 0 to 40 °C and 40 to 60 °C, the permissible range is 5 mA to 0.6 A.
4. Does it provide short-circuit protection and diagnostics?
It has electronic short-circuit protection. It has no diagnostics function, diagnostic alarm, wire-break diagnosis, short-circuit diagnosis, fuse-blown diagnosis, or missing-load-voltage diagnosis.
5. What is excluded from the supplied configuration?
The configuration is without alarms, diagnostics indication for rated load voltage PWR, and fuse OK FSG indication.