Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Analog output channels | 4; Isochronous mode |
| Voltage output ranges | 0 to 10 V; 1 V to 5 V; -10 V to +10 V |
| Current output ranges | 0 to 20 mA; 4 mA to 20 mA; -20 mA to +20 mA |
| Resolution with overrange | 16 bit including sign |
| Rated load voltage | 24 V DC |
| Conversion time | 200 μs per channel; 640 μs in isochronous mode |
| Voltage load impedance | 1 kΩ min. |
| Current load impedance | 500 Ω max. |
| Actuator connections | Four-wire for voltage output; two-wire for current output |
| Channel isolation | Between the channels; between the channels and backplane bus; between the channels and the electronics power supply |
| Diagnostics | Parameterizable substitute values; diagnostic alarm; red group error SF LED |
| Isolation test | 1 500 V DC |
Applications
- Analog voltage output: Provides analog voltage output through four-wire actuator connections.
- Analog current output: Provides analog current output through two-wire actuator connections.
Key Features
- Analog outputs: 4 analog outputs with channel-to-channel potential separation and isochronous mode.
- Supported output ranges: Voltage: 0 to 10 V, 1 V to 5 V, and -10 V to +10 V. Current: 0 to 20 mA, 4 mA to 20 mA, and -20 mA to +20 mA.
- Resolution and conversion: Resolution with overrange: 16 bit including sign. Conversion time is 200 μs per channel, or 640 μs in isochronous mode.
- Supply and protection: Rated load voltage is 24 V DC with reverse polarity protection. Voltage output short-circuit protection is provided; maximum short-circuit current is 40 mA.
- Connections and load: Voltage output uses a four-wire actuator connection; current output uses a two-wire connection. Voltage load impedance is at least 1 kΩ, and current load impedance is at most 500 Ω.
- Diagnostics and isolation: Parameterizable substitute values, diagnostic alarm, and red group error SF LED are supported. Isolation is tested with 1 500 V DC.
Frequently Asked Questions
1. How many analog output channels does Siemens 6AG1332-7ND02-4AB0 have?
It has 4 analog outputs with channel-to-channel potential separation and supports isochronous mode.
2. Which output ranges does this module support?
Voltage ranges are 0 to 10 V, 1 V to 5 V, and -10 V to +10 V. Current ranges are 0 to 20 mA, 4 mA to 20 mA, and -20 mA to +20 mA.
3. What connections are used for the analog outputs?
Voltage output uses a four-wire actuator connection, while current output uses a two-wire actuator connection. The module has a 20-pole connection.