Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Module | SINAMICS Power Module PM240-2 |
| Supply | 200-240 V 1/3AC+10/-10%, 47-63Hz |
| High overload power | 1.5 kW at 200% 3 s, 150% 57 s, 100% 240 s; ambient temperature -10 to +50 °C |
| Low overload power | 2.2 kW at 150% 3 s, 110% 57 s, 100% 240 s; ambient temperature -10 to +40 °C |
| Integrated components | Class A filter and braking chopper |
| Degree of protection | IP20-PT |
| Included equipment | Without Control Unit and operation panel |
| Firmware status | Released as of CU Firmware version V4.6 |
| Lifecycle | Product cancellation |
Key Features
- Power module type: SINAMICS Power Module PM240-2 with an integrated Class A filter and integrated braking chopper.
- Supply: 200-240 V 1/3AC+10/-10% at 47-63Hz.
- High overload power: 1.5 kW at 200% for 3 s, 150% for 57 s, and 100% for 240 s; ambient temperature -10 to +50 °C.
- Low overload power: 2.2 kW at 150% for 3 s, 110% for 57 s, and 100% for 240 s; ambient temperature -10 to +40 °C.
- Form factor and protection: FSB dimensions: 345 x 154 x 171 mm (HxWxD); degree of protection IP20-PT.
- Configuration and lifecycle: Without Control Unit and operation panel; Product cancellation. Released as of CU Firmware version V4.6.
Frequently Asked Questions
1. What is the function of 6SL3211-1PB21-0AL0?
It is a SINAMICS Power Module PM240-2 with an integrated Class A filter and braking chopper.
2. What supply does this Power Module use?
Supply is 200-240 V 1/3AC+10/-10% at 47-63Hz.
3. What are the high and low overload power ratings?
High overload power is 1.5 kW at 200% for 3 s, 150% for 57 s, and 100% for 240 s at -10 to +50 °C. Low overload power is 2.2 kW at 150% for 3 s, 110% for 57 s, and 100% for 240 s at -10 to +40 °C.
4. What is included in this configuration?
It is without a Control Unit and operation panel.
5. What are the dimensions and protection degree?
The FSB dimensions are 345 x 154 x 171 mm (HxWxD), with degree of protection IP20-PT.