Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Module type | SIPLUS S7-300 digital output module |
| Digital outputs | 16 |
| Rated load voltage | 24 V DC |
| Rated output current, signal "1" | 0.5 A |
| Permissible load voltage range | 20.4 V to 28.8 V |
| Short-circuit protection | Yes |
| Diagnostic information | Wire break, short-circuit, and missing load voltage |
| Connection | 1x 40-pole |
| Required connection | IM 153-X HF |
| Horizontal installation maximum current | 2 A up to 60 °C; 0.5 A up to 70 °C |
| Vertical installation maximum current | 2 A up to 40 °C |
| Conformal coating | Yes |
Applications
- Digital output control: Controls digital output signals through 16 channels with a 24 V DC supply and diagnostics for wire break, short-circuit, and missing load voltage.
Key Features
- Digital outputs: Has 16 digital outputs with 24 V DC signal supply and 0.5 A rated output current.
- Output protection: Provides short-circuit protection and inductive shutdown voltage limitation to L+ (-68 V).
- Diagnostics: Supports diagnostic alarms and readable diagnostic information for wire break, short-circuit, and missing load voltage.
- Electrical separation: Digital outputs are electrically separated from the backplane bus, but not between channels or from the electronics power supply.
- Connection: Has a 1x 40-pole connection; connection IM 153-X HF is required.
- Installation limits: For horizontal installation, maximum current is 2 A up to 60 °C and 0.5 A up to 70 °C; for vertical installation, maximum current is 2 A up to 40 °C.
Frequently Asked Questions
1. How many digital outputs does the 6AG1322-8BH10-7AB0 have?
It has 16 digital outputs.
2. What output current does this module provide?
The rated output current for signal "1" is 0.5 A, with a permissible range of 5 mA to 0.6 A.
3. What diagnostics are available?
It provides diagnostic information for wire break, short-circuit, and missing load voltage, along with diagnostic alarms.
4. What connection is required for this configuration?
It has a 1x 40-pole connection, and connection IM 153-X HF is required.