6SL3210-1PE32-5AL0

Siemens 6SL3210-1PE32-5AL0 SINAMICS G120 PM240-2 power module with integrated Class A filter and braking chopper, 132.00 kW LO or 110.00 kW HO. Request a model-specific quote.

Product Code
6SL3210-1PE32-5AL0
Dimensions
74.5 × 46.9 × 38.5 cm
Weight
70.75 kg
Lifecycle
Active Product
Availability
in stock
Lead Time
Confirmed with quotation
Product Attachment
Download Datasheet
Request Current Quote

Current status: in stock. Price, condition, lead time and warranty are confirmed in the quotation.

Product Overview

Technical Summary

Parameter Value
Rated output power (LO) 132.00 kW | 200.00 hp
Rated output power (HO) 110.00 kW | 150.00 hp
Input supply 3 AC, 380 … 480 V ±10 %, 47 … 63 Hz
Rated output current (LO) 250.00 A
Rated output current (HO) 205.00 A
Maximum output current 410.00 A
Output frequency for vector control 0 … 200 Hz
Output frequency for V/f control 0 … 550 Hz
Integrated filter Class A
Braking chopper Built-in
Protection IP20 / UL open type
Frame size FSF

Key Features

  1. Power ratings: Rated output power: 132.00 kW | 200.00 hp (LO) or 110.00 kW | 150.00 hp (HO).
  2. Input supply: Input: 3 AC, 380 … 480 V ±10 %, 47 … 63 Hz.
  3. Output performance: Output: 3 AC, rated voltage 400V IEC | 480V NEC, maximum output current 410.00 A.
  4. Control frequency ranges: Output frequency: 0 … 200 Hz for vector control and 0 … 550 Hz for V/f control.
  5. Integrated components: Built-in Class A filter and braking chopper; the configuration is without control unit and panel.
  6. Connections and installation: Line-side and motor-end connections use M10 bolts; protection is IP20 / UL open type, with FSF frame size and dimensions of 305 mm × 708 mm × 357 mm (W × H × D).

Frequently Asked Questions

1. What is the rated power of Siemens 6SL3210-1PE32-5AL0?

Rated output power is 132.00 kW | 200.00 hp in LO or 110.00 kW | 150.00 hp in HO.

2. What input supply does this power module use?

It uses 3 AC input at 380 … 480 V ±10 % and 47 … 63 Hz.

3. What output frequency ranges are supported?

The output frequency is 0 … 200 Hz for vector control and 0 … 550 Hz for V/f control.

4. Which components are included in the configuration?

It has a built-in Class A filter and braking chopper. It is without control unit and panel.

5. How is the module connected and protected?

Line-side and motor-end connections use M10 bolts. Protection is IP20 / UL open type.

Send Inquiry