6ES7144-5KD50-0BA0

Siemens SIMATIC ET 200AL analog input module with 4 RTD/TC channels, 4x M12 connections, 16-bit resolution and IP67 protection. Request a model-specific quote.

Product Code
6ES7144-5KD50-0BA0
Dimensions
17.8 × 4.7 × 4 cm
Weight
0.188 kg
Lifecycle
Active Product
Availability
in stock
Lead Time
Confirmed with quotation
Product Attachment
Download Datasheet
Request Current Quote

Current status: in stock. Price, condition, lead time and warranty are confirmed in the quotation.

Product Overview

Technical Summary

Parameter Value
Product type AI 4xRTD/TC
Analog input channels 4
Supported voltage input range -80 mV to +80 mV
Resolution 16 bit including sign
Load voltage 1L+ 24 V rated; permissible range 20.4 V to 28.8 V
Connections 4x M12
Protection IP67
Cycle time, all channels 90 ms
Integration time 16.7 / 20 / 60 ms, parameterizable channel by channel
Diagnostics Wire break, overflow/underflow, diagnostic alarm and limit value alarm
Firmware version V2.0.x

Applications

  1. Analog signal measurement: Measures voltage, resistance, resistance thermometer and thermocouple signals through 4 analog inputs.

Key Features

  1. Analog input channels: 4 analog inputs support voltage, resistance, resistance thermometer and thermocouple measurement.
  2. Signal ranges and resolution: The module supports -80 mV to +80 mV voltage input and 16 bit including sign; supported resistance thermometer types include Ni 100, Ni 1000, Pt 100 and Pt 1000.
  3. M12 connections and protection: The module has 4x M12 connections and IP67 degree of protection.
  4. Supply and consumption: Load voltage 1L+ is 24 V rated, with a permissible range of 20.4 V to 28.8 V; current consumption is 30 mA without load.
  5. Diagnostics and isolation: Parameterizable diagnostic and limit value alarms are available; wire-break and overflow/underflow diagnoses are supported. Channels are isolated from the backplane bus.
  6. Configurable conversion: Integration time is parameterizable channel by channel, with 16.7 / 20 / 60 ms settings; measured-value smoothing is parameterizable.

Frequently Asked Questions

1. How many analog inputs does the 6ES7144-5KD50-0BA0 have?

It has 4 analog inputs.

2. Which signals can this module measure?

It supports voltage, resistance, resistance thermometer and thermocouple measurement.

3. What voltage input range and resolution are supported?

The voltage input range is -80 mV to +80 mV, with 16 bit including sign.

4. What connection and protection details should be checked?

The module has 4x M12 connections and IP67 degree of protection.