Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Module type | SINAMICS G120 PM230 Power Module |
| Supply | 380-480 V 3AC +10/-10% |
| Frequency | 47-63 Hz |
| Low-overload power | 37 kW |
| Low-overload capacity | 110% for 60 s; 100% for 240 s |
| Ambient temperature | 0 to +40 °C (LO) |
| Protection | IP20 |
| Filter | Integrated class A filter |
| Configuration | FSE without Control Unit and operating unit |
| Released for Control Units | CU240B/E-2 and CU230P-2 |
| Firmware requirement | V4.4 or higher |
| Safety | No safety supported |
Key Features
- Power Module function: SINAMICS G120 PM230 Power Module for power conversion in a spare-part configuration.
- Supply and frequency: Supply: 380-480 V 3AC +10/-10%; frequency: 47-63 Hz.
- Low-overload rating: Low overload: 37 kW at 110% for 60 s and 100% for 240 s.
- Protection and filter: Integrated class A filter; degree of protection: IP20.
- Ambient temperature: Ambient temperature: 0 to +40 °C (LO).
- Configuration and firmware: FSE configuration without Control Unit and operating unit; released for CU240B/E-2 and CU230P-2 with firmware version V4.4 or higher. No safety is supported.
Frequently Asked Questions
1. What power rating does the 6SL3210-1NE27-5AL0 PM230 support?
It supports 37 kW at low overload, with 110% for 60 s and 100% for 240 s.
2. What supply does the 6SL3210-1NE27-5AL0 require?
The supply is 380-480 V 3AC +10/-10% at 47-63 Hz.
3. What is included in the 6SL3210-1NE27-5AL0 configuration?
It is an FSE configuration without a Control Unit and operating unit. No safety is supported.