3RW4447-6BC44

Siemens 3RW4447-6BC44 SIRIUS soft starter with 432 A at 40 °C in standard circuit, 230 V AC control supply, screw terminals, and 3 NO contacts. Request a model-specific quote.

Product Code
3RW4447-6BC44
Dimensions
43.2 × 34.8 × 36.6 cm
Weight
11.53 kg
Lifecycle
Start of final year of support
Availability
in stock
Lead Time
Confirmed with quotation
Product Attachment
Download Datasheet
Request Current Quote

Current status: in stock. Price, condition, lead time and warranty are confirmed in the quotation.

Product Overview

Technical Summary

Parameter Value
Rated operational current at 40 °C, standard circuit 432 A
Rated operational current at 40 °C, inside-delta circuit 748 A
Rated motor power at 400 V, standard circuit 250 kW
Rated motor power at 400 V, inside-delta circuit 400 kW
Operating voltage 200 … 460 V
Control supply voltage 230 V AC at 50 Hz and 60 Hz
Main current circuit connection Busbar connection
Auxiliary and control circuit connection Screw-type terminals

Key Features

  1. Rated operational current: 432 A at 40 °C, 385 A at 50 °C, and 335 A at 60 °C in standard circuit.
  2. Inside-delta current: 748 A at 40 °C, 667 A at 50 °C, and 580 A at 60 °C for 3-phase motors in inside-delta circuit.
  3. Motor protection and control: Has intrinsic device protection, motor overload protection, evaluation of thermistor motor protection, external reset, and adjustable current limitation.
  4. Control supply: AC control supply with 230 V at 50 Hz and 60 Hz; the supply frequency has a -10 % to 10 % tolerance.
  5. Electrical connections: Uses busbar connection for the main current circuit and screw-type terminals for auxiliary and control circuits.
  6. Mounting and protection: Screw fixing; 210 mm wide, 230 mm high, and 298 mm deep. Front protection is IP00, or IP20 with box terminal/cover.

Frequently Asked Questions

1. What rated current does the Siemens 3RW4447-6BC44 provide?

It provides 432 A at 40 °C, 385 A at 50 °C, and 335 A at 60 °C in standard circuit.

2. What control supply and connections does this soft starter use?

It uses a 230 V AC control supply at 50 Hz or 60 Hz, with busbar connection for the main current circuit and screw-type terminals for auxiliary and control circuits.

3. What mounting clearances are required for the 3RW4447-6BC44?

With side-by-side mounting, required spacing is 100 mm upwards, 5 mm at the side, and 75 mm downwards. The device uses screw fixing.