Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Module type | CP 342-5 communications processor |
| PROFIBUS transfer rate | 9.6 kbit/s … 12 Mbit/s |
| PROFIBUS electrical connection | 1 × 9-pin Sub-D socket (RS485) |
| External supply | 24 V DC |
| Backplane-bus supply | 5 V DC |
| DP master capacity | 124 operable DP devices |
| Open communication connections | 16 maximum |
| Module format | Compact module S7-300 single width |
Applications
- SIMATIC S7-300 to PROFIBUS DP connection: Connects SIMATIC S7-300 to PROFIBUS DP for DP master and DP device communication.
- S7 communication: Provides S7 communication and PG/OP communication.
- Open communication: Supports open communication by means of SEND/RECEIVE blocks.
Key Features
- PROFIBUS DP communications processor: CP 342-5 for connecting SIMATIC S7-300 to PROFIBUS DP, with S5-compatible, PG/OP and S7 communication.
- PROFIBUS interface: 1 electrical connection via a 9-pin Sub-D socket (RS485); transfer rate: 9.6 kbit/s … 12 Mbit/s.
- Power connections and supply: 1 power-supply connection via a 4-pole terminal block; supply: DC, 5 V from the backplane bus and 24 V external.
- Communication capacity: Up to 124 operable DP devices as DP master, 16 connections for open communication, and 16 S7 communication connections.
- Conformal coating and protection: Conformal coating, class A; IP20 protection class. Supplied plug covers must remain in place on unused interfaces during operation.
- Compact S7-300 format: Compact module S7-300 single width; 40 mm wide, 125 mm high, 120 mm deep, with a net weight of 0.3 kg.
Frequently Asked Questions
1. What is the function of 6AG1342-5DA03-7XE0?
It is a SIPLUS NET CP 342-5 communications processor for connecting SIMATIC S7-300 to PROFIBUS DP, with S5-compatible, PG/OP and S7 communication.
2. What PROFIBUS interface and transfer rate does it have?
It has 1 9-pin Sub-D socket (RS485), with a transfer rate of 9.6 kbit/s … 12 Mbit/s.
3. What supply connections are provided?
It has 1 4-pole terminal block for the power supply, with 5 V from the backplane bus and 24 V external DC supply.
4. Does it support TCP/IP or Industrial Ethernet?
TCP/IP is not supported, and the number of interfaces according to Industrial Ethernet is 0.